![Savch S200 Series User Manual Download Page 13](http://html.mh-extra.com/html/savch/s200-series/s200-series_user-manual_1203756013.webp)
9
Applicable electromagnetic contactor and wiring specifications
Non-fuse breaker/Magnetic contactor
SAVCH ELECTRIC shall not be responsible for faults due to the following:
(1) Absence or inapplicable or over large non fuse breakers was put between the power supply and the inverter,
which results in the inverter fault
(2) Magnetic contactors or advance capacitor or Surge Absorber were connected in series between the inverter
and motor
● A three phase Squirrel-cage induction motor which corresponds with the capacity of the inverter shall be
adopted.
● If more than one motor were driven simultaneously by one inverter, the current of these motors when running
shall below capacity of the inverter. And each motor shall be prepared with a thermal relay in appropriate capacity.
● Phase advance capacitors and other capacity elements such as LC or RC shall not be fixed between the
inverter and motor.
List of applicable no-fuse breaker for S200 series
440V Series
S200-
SERIES MODEL
Rated Input
Current(A)
Rated Output
Current(A)
Motor
Output(kW)
Non-fuse Switch Rated
Current(A)
S200-4T0.75G
4.2
3.0
0.75
5
S200-4T1.5G
5.8
4.2
1.5
10
S200-4T2.2G
7.2
5.5
2.2
15
S200-4T3.7G
8.5
8.2
3.7
20
S200-4T4.0G
11.2
9.7
4.0
20
S200-4T5.5G
14
13
5.5
20
S200-4T7.5G
20.6
18
7.5
30
S200-4T11G/P
28
24
11
50
S200-4T15G/P
30
32
15
60