68
Part IV
Signals
NRT407 manual
Chapter 18
BACnet signal types
BACnet
In order to communicate via BACnet, the protocol has to be changed either via NRT tool
©
or
via the parameter list in the display. Once the protocol has been set to BACnet it can only be
switched back to Modbus via the display.
MS/TP mode
Both MS/TP master and slave are supported. The mode is controlled by setting the MAC
address. If < 127, master mode is selected. A MAC address of > 127 enables slave.
Object Type
The BACnet types of the signals (types in the list below):
•
Analogue inputs
•
Analogue values
•
Binary inputs
•
Binary values
•
Loop
•
Multistate inputs
•
Multistate values
•
Device
Out_of_service
The property out_of_service is not writable for all Object Types.
Commandable
The value objects are not commandable (i.e. does not use a priority array).