It is possible to set different parameter values in a parameter menu. The parameter menu is
accessed by simultaneously holding the INCREASE and DECREASE buttons depressed for
about 5 seconds and then pressing the INCREASE button twice. The Service indication will
be displayed.
The display will initially show the parameter number “1”. Use the INCREASE and
DECREASE buttons to scroll between parameters.
Press the Occupancy button to select the desired parameter. The parameter number will be
replaced by the parameter value. The value can be changed using the INCREASE and
DECREASE buttons. If a button is held depressed the value will start scrolling, first slowly
and then with increasing speed in 3 – 4 steps with 2 – 3 seconds between steps.
Acknowledge/Regret
To acknowledge and store a set parameter value, press the Occupancy button again, the
display then returns to showing the parameter number. To retrieve the original value, i.e. the
value before change, press the INCREASE and DECREASE buttons at the same time. The
original value is shown on the display.
Return
After a certain time, about 1 minute, or when the INCREASE and DECREASE buttons are
pressed at the same time while in the menu, the display returns to the normal view. Exit is
shown on the display after the last parameter. The parameter menu is exited by pressing the
Occupancy button while in Exit. Pressing on INCREASE goes to the first parameter and
pressing on DECREASE goes to the last parameter.
Parameters
The following parameters can be changed in the parameter menu (FS = Factory setting):
Parameter
number
Description
FS
1
Basic heating setpoint
22°C
2
Basic cooling setpoint
24°C
3
Neutral zone at standby,
Heating setpoint = Basic sp. heating-3 by default
Cooling setpoint = Basic sp.3 by default
3°C
4
Heating setpoint at Unoccupied
15°C
5
Cooling setpoint at Unoccupied
30°C
6
Frost protection setpoint
8°C
7
P-band for room controller
10°C
8
I-time for room controller
300 s
9
The difference between the temperature in the room and the media
temperature for change-over to cooling
3K
10
The difference between the temperature in the room and the media
temperature for change-over to heating
4K
11
Control mode:
0=Heating
1= Heating / Heating
2= Heating or Cooling via change-over
3= Heating / Cooling
4= Heating / Cooling with VAV-control and forced ventilation
5= Heating / Cooling with VAV-control
6= Cooling
7= Cooling / Cooling
8= Heating / Cooling/VAV (C3-models, except NRT407F902)
9=Heating / Heating or Cooling via change-over (only available on models
with fan control)
3
12
Time in Bypass mode
120 min
13
Disconnect timer with Occupancy/Unoccupancy
10 min
14
Switch-on delay for Occupancy
0 min
15
State connected sensor on AI1:
0=Internal sensor
1=External room sensor
2=Change-over sensor (NRT407F901 / F902)
0
Summary of Contents for NRT407
Page 1: ...SAUTER ITALIA SPA NRT407 ...
Page 9: ...NRT407 manual Part I Introduction 9 Design NRT407F902 NRT407F901 ...
Page 13: ...NRT407 manual Part I Introduction 13 ...
Page 46: ...46 Part III Configuration NRT407 manual Chapter 13 Indications ...
Page 54: ......
Page 73: ...NRT407 manual Part IV Signals 73 ...
Page 76: ...SAUTER your local partner www sauteritalia it ...