Signal name
Type Modbus
address
Default
value
Description
RC_Setp_X.NRTUo1
X, 3
42
3
State connected function on UO1:
0=None
1=Thermal actuator heat
2=None
3=Heating actuator 0...10 V
4=None
5=On/off actuator heat
6=None
RC_Setp_X.NRTUo2
X, 3
43
4
State connected function on UO2:
0=None
1=None
2=Thermal actuator Cool
3=None
4=Cooling actuator 0…10 V
5=None
6=On/off actuator cool
RC_Setp_X.NRTModbusSlaveAddr
X, 3
44
Factory
set
Controller Modbus address
RC_Setp_X.NRTModbusParity
X, 3
45
2
Parity of Modbus communication:
0=No parity
1=Odd parity
2=Even parity
RC_Setp_X.NRTModbusCharTimeout
X, 3
46
3 ms
Modbus timeout for character
(t1.5), in ms. Should be 1.5 times a
character, i.e. at least 2 ms.
RC_Setp_X.NRTModbusAnswerDelay
X, 3
47
5 ms
Answer delay in Modbus (t3.5), in
ms. Should be 3.5 times a
character, i.e. at least 5 ms.
RC_Setp_X.NRTDispBacklightLO
X, 3
48
10
10=Backlight low
RC_Setp_X.NRTDispBacklightHi
X, 3
49
30
30=Backlight high
RC_Setp_X.NRTDispContrast
X, 3
50
15
15=Display contrast
RC_Setp_X.NRTDisplayViewMode
X, 3
51
0
Select if setpoint or actual value is
to be shown in the display.
0=Actual value
1=Heat setpoint
2=Cool setpoint
3=Average value of heating and
cooling setpoint
4=Only setpoint offset
5=CO
2
-concentration in the room
in ppm (NRT407F901 / F902)
6=Heating sesetpoint offset
7=Cooling ssetpoint offset
8=Average of heating and cooling
ssetpoint offset
9=The calculated flow in the duct
in l/s (NRT407F901 / F902)
Summary of Contents for NRT407
Page 1: ...SAUTER ITALIA SPA NRT407 ...
Page 9: ...NRT407 manual Part I Introduction 9 Design NRT407F902 NRT407F901 ...
Page 13: ...NRT407 manual Part I Introduction 13 ...
Page 46: ...46 Part III Configuration NRT407 manual Chapter 13 Indications ...
Page 54: ......
Page 73: ...NRT407 manual Part IV Signals 73 ...
Page 76: ...SAUTER your local partner www sauteritalia it ...