62
Part IV
Signals
NRT407 manual
Signal name
Type Modbus
address
Default
value
Description
RC_Setp_X.NRTUnitReturnState
X, 3
15
3
Preset operating mode:
0=Off
1=Unoccupied
2=Stand-by
3=Occupied. Forced ventilation is
not set in Occupied mode.
RC_Setp_X.NRTUnitShutDownState
X, 3
16
1
State operating mode by pressing
the occupancy button for 5 s:
0=Off
1=Unoccupied.
RC_Setp_X.NRTBtnOnOffTime
X, 3
17
5 s (0 s
for F902
models)
Time to keep the occupancy button
depressed before switching to
Shutdown state.
RC_Setp_X.NRTControllerMode
X, 3
18
3
Control mode:
0=Heating
1= Heating / Heating
2= Heating or Cooling via change
over
3= Heating /Cooling
4= Heating /Cooling with VAV-
control and forced supply air
function
5= Heating /Cooling with VAV-
control
6= Cooling
7= Cooling/Cooling
8= Heating /Cooling/VAV (except
NRT407F902)
9=Heating/Heating or Cooling via
change-over (only available in
models with fan control)
RC_Setp_X.NRTCVHeatType
X, 3
19
0
State output signal range for
Heating-actuators:
0=0…10 V
1=2…10 V
2=10…2 V
3=10…0 V
RC_Setp_X.NRTCVCoolType
X, 3
20
0
State output signal range for
Cooling actuators:
0=0…10 V
1=2…10 V
2=10…2 V
3=10…0 V
RC_Setp_X.NRTCVHeatExerciseInterval
X, 3
21
23h
Time in hours between exercise of
heating actuators
RC_Setp_X.NRTCVCoolExerciseInterval
X, 3
22
23h
Time in hours between exercise of
cooling actuators
Not used in this model
X, 3
23
-
RC_Setp_X.NRTAi1
X, 3
24
0
State connected sensor on AI1:
0=Internal sensor
1=External room sensor
2=Change over sensor
(NRT407F901 / F902)
Summary of Contents for NRT407
Page 1: ...SAUTER ITALIA SPA NRT407 ...
Page 9: ...NRT407 manual Part I Introduction 9 Design NRT407F902 NRT407F901 ...
Page 13: ...NRT407 manual Part I Introduction 13 ...
Page 46: ...46 Part III Configuration NRT407 manual Chapter 13 Indications ...
Page 54: ......
Page 73: ...NRT407 manual Part IV Signals 73 ...
Page 76: ...SAUTER your local partner www sauteritalia it ...