Holding register
Signal name
Type Modbus
address
Default
value
Description
RC_Setp_X.AlaModStat
X, 3
1
-
Not used
RC_SetP_X.NRTFreeCoolAvailable
X, 3
2
0
Sequence order for Y2 and Y3:
0=Y2 activates before Y3
1=Y3 activates before Y2
RC_Setp_X.NRTHeatOutputSelect
X, 3
3
2
Manual/Auto Heating output:
0=Off
1=Manual
2=Auto
RC_Setp_X.NRTCoolOutputSelect
X, 3
4
2
Manual/Auto Cooling output:
0=Off
1=Manual
2=Auto
RC_Setp_X.NRTFanSelect
X, 3
5
4
Select fan mode:
0 = Off
1 = Manual speed 1
2 = Manual speed 2
3 = Manual speed 3
4 = Auto
RC_Setp_X. NRTFanControlMode
X, 3
6
3
Configuration of fan control:
0=No control
1=Fan is controlled by heating
demand
2=Fan is controlled by cooling
demand
3=Fan is controlled by both
heating and cooling demand
RC_Setp_X.NRTFanSpeed1Start
X, 3
7
5 %
Start signal in % for fan speed 1 on
heating or cooling control
RC_Setp_X.NRTFanSpeed2Start
X, 3
8
60 %
Start signal in % for fan speed 2
RC_Setp_X.NRTFanSpeed3Start
X, 3
9
100 %
Start signal in % for fan speed 3
RC_Setp_X.NRTFanSpeedHyst
X, 3
10
5 %
Hysteresis for start/stop of fans
RC_Setp_X.NRTFanSpeedMax
X, 3
11
3
State number of speeds for the fan
RC_Setp_X.NRTForcedVentSelec
X, 3
12
2
Manual/Auto Y3 forced ventilation
output:
0=Off
1=Manual
2=Auto
RC_Setp_X.NRTChangeOverSelect
X, 3
13
2
Manual/Auto control of change-
over mode:
0=Heat control
1=Cool control
2=Automatic change over
depending on analogue sensor
input or digital input
RC_Setp_X.NRTRemoteState
X, 3
14
5
Select operating mode for central
control:
0=Off
1=Unoccupied
2=Stand-by
3=Occupied
5=No central control
Summary of Contents for NRT407
Page 1: ...SAUTER ITALIA SPA NRT407 ...
Page 9: ...NRT407 manual Part I Introduction 9 Design NRT407F902 NRT407F901 ...
Page 13: ...NRT407 manual Part I Introduction 13 ...
Page 46: ...46 Part III Configuration NRT407 manual Chapter 13 Indications ...
Page 54: ......
Page 73: ...NRT407 manual Part IV Signals 73 ...
Page 76: ...SAUTER your local partner www sauteritalia it ...