Rx- -----|
Bitrate, two stop bits, parity is the next layer
These settings must correspond to the settings in the master unit. Find out how the master is
set and then give the Controller the same settings.
Parity can be set to odd, even (FS) or none. If none is chosen, two stop bits will
automatically be used. If odd or even is chosen, only one stop-bit is used, or there will be too
many bits altogether: 1 start-bit, 8 data-bits, 1 parity-bit and 1 stop-bit give a total of 11 bits
which is the maximum amount.