38
Part III
Configuration
NRT407 manual
Setpoint display at
setpoint adjustment
Parameter 74 is used to set what is shown in the display when the setpoint is adjusted.
0 = The added adjustment is shown in the display. Example: +1.5°C. The adjustment is
added to both the heating and cooling setpoints.
1 = The sum of the control setpoint and the adjustment is shown in the display. Example:
The control setpoint is 22°C and the added adjustment is +1.5°C. This means that the
value 23.5°C will be shown in the display. ”HEAT” or ”COOL” will flash
depending on which of the setpoint values is the control setpoint when you enter the
setpoint menu, i.e. depending on which setpoint you are changing. The adjustment is
added to both the heating and cooling setpoints.
2 = The sum of the heating setpoint and the adjustment is shown in the display. The
adjustment is added to both the heating and cooling setpoints.
3 = The sum of the cooling setpoint and the adjustment is shown in the display. The
adjustment is added to both the heating and cooling setpoints.
Summary of Contents for NRT407
Page 1: ...SAUTER ITALIA SPA NRT407 ...
Page 9: ...NRT407 manual Part I Introduction 9 Design NRT407F902 NRT407F901 ...
Page 13: ...NRT407 manual Part I Introduction 13 ...
Page 46: ...46 Part III Configuration NRT407 manual Chapter 13 Indications ...
Page 54: ......
Page 73: ...NRT407 manual Part IV Signals 73 ...
Page 76: ...SAUTER your local partner www sauteritalia it ...