NRT407 manual
Part II
Installation
19
Wiring for NRT407F901
Figure 8. Connection diagrams for model for CO
2
control
Terminal
Designation
Operation
10
G
Supply voltage 24 V AC
11
G0
Supply voltage 0 V
12-14
No function.
20
GDO
24 V AC out common for DO. Internally connected to terminal 10, G.
21
G0
0 V common for UO. Internally connected to terminal 11, G0.
22
UO3
Output for VAV or EC-fan.
For forced ventilation. 24 V AC output, max. 2.0 A. 24 V actuator is
connected between terminal 22 and terminal 20, GDO.
alternatively
For 0…10 V DC damper control/EC-fan. The damper actuator/EC-fan
0…10 V control signal terminal is connected to terminal 22 and its supply
terminals to terminals 10 and 11. Make sure that the reference pole G0 is
connected to the correct terminal on the actuator.