Wiring for NRT407F902
Figure 9. Connection diagrams for models for CO
2
control and fan control
Terminal Designation
Operation
10
G
Supply voltage 24 V AC
11
G0
Supply voltage 0 V
12-14
No function.
20
GDO
24 V AC out common for DO. Internally connected to terminal 10, G.
21
G0
0 V common for UO. Internally connected to terminal 11, G0.
22
UO3
Control EC fan, 0…10 V DC.
23
UO1
Control output heating (FS), cooling or heating or cooling via change-over.
For a 0...10 V DC valve actuator, max 5 mA (FS). The valve actuator’s 0…10
V control signal terminal is connected to terminal 23 and its supply terminals to
terminals 10 and 11. Make sure that the reference pole G0 is connected to the
correct terminal on the actuator.
alternatively
For a 24 V AC thermal actuator, max 2.0 A. The thermal actuator is connected
between terminals 23 and 20, GDO.
alternatively
For a 24V AC actuator with spring return, max. 2.0 A. The actuator is
connected between terminals 23 and 20. This can be configured either through
the display or through NRT tool. The output signal for UO1 can be set to NC
(normally closed) or NO (normally open).