Inquiry and adaptation of user adjustment values PAR (parameters)
The following tables provide information on the available user adjustment values. The adjustment value in the second column
(
) corresponds to the factory settings. The numbers in parentheses indicate the range within which the corresponding
adjustment value can be specified.
Key
Function
Call the first user adjustment value
Inquire the next adjustment value (page forward)
Inquire the next adjustment value (page backward)
Clear the value shown on the display (if required)
...
Enter valid value
Return to the desired operating mode by pressing the corresponding key or with automatic return to
the last mode after approx. 2 minutes.
PAR
Setting value
No.
Function
1
20.0 ° C Room temperature setpoint during normal operation (
), (= base point T
I
of the heating characteristic for
normal operation)
(5.0...39.9 ° C)
2
12.0 ° C Room temperature setpoint during reduced operation (
), (= base point T
I
of the heating characteristic
during reduced operation)
(5.0...39.9 ° C)
3
1.40
Slope of the heating characteristic
The heating characteristic specifies the setpoint of the secondary flow temperature dependent on the outdoor
temperature.
The heating characteristic is primarily determined by its base point T
I
(=PAR 1) and its slope.
For qualitative considerations, the following applies:
Small heating surfaces require higher flow temperatures, while large heating surfaces require lower flow
temperatures in order to provide a certain heat output.
Slope guidelines:
Hot-water radiator heating
1,4
Low-temperature heating
1,0
Floor heating system
0,6
After correcting base point or slope, the building (and probably the heating system) requires a certain period of
time to adjust itself to the correction value. Therefore, only one correction should be executed per day (refer
also to section "Adapting the heating characteristic").