Specialist’s information
Inquiry and adjustment of SERV service settings
Service settings are closely related to the safety of the heating
system and may only be adjusted by trained specialists. For
modifications, the sliding switch (
,AUTO,
) must be pushed
to its
position. The values can also be inquired in "AUTO"
position.
SERV (= Service) settings
The service settings are classified in the following groups
As a rule, only the setting values required by the controller
according to its configuration are displayed
The following tables provide information on the available
SERVice setting values. The value in the second column (
)
corresponds to the factory setting. The numerical values in pa-
rentheses indicate the range within which the setting value can
be specified.
Key
Function
...
Call the first service setting value (enter the numerical code)
Inquire the next setting value (page forward)
Inquire the next setting value (page backward)
Move switch to the key position
Clear the value shown on the display (if required)
...
Enter valid value.........
Return to the desired operating mode by pressing the corresponding key or with
automatic return to the last mode after approx. 2 minutes
SERV- no.
Function
Page
00...09
Configuration ot outputs, running times of valve actuators, follow-up time of pumps
27
10...18
Input alignment
30
19...30
Configuration of inputs
32
31...39
Setting values with regard to limiting functions for "flow rate" and "return temperature"
35
40...49
Setting values with regard to control via valve V1
37
50...59
Setting values with regard to control via valve V2
38
60...89
Setting values with regard to heating system, building and air conditioning
39
90...96
Setting values with regard to domestic hot water
47
97...98
Pre-control with 2 valves in series
47
0
0
0
9
9
AUTO
0
9
1
A considerable number of the controller adjustment values refer to controller parametering. We therefore recommend that
the configuration sheets attached at the end of these operating instructions be completed/amended when changing SERVice
setting values (taking into consideration the system layout at the place of installation of the controller.