2-point output configuration
The two-point outputs (terminals 7, 6, 4, 3) can be configured according to the following table (setting values SERV 04...07).
–1
=
No function (output is not used)
+00
=
Time channel to exterior. ON (= 1) and OFF (= 0) commands can be entered in the time
programs. Using these commands, any load can be switched on and off in a time-
dependent pattern, independent from the heating system (time-switch function).
+01
=
Actuation of the circulation pump of heating circuit 1 (UP1). UP1 is always assigned to
heating circuit 1.
+02
=
Actuation of the circulation pump of heating circuit 2 (UP2). UP2 is always assigned to
heating circuit 2.
+03
=
LP 1 charges either the domestic-hot-water tank or a heat exchanger for domestic-
hot-water charging.
+04
=
Actuation of the domestic-hot-water circulation pump. ON (= 1) or OFF (= 0) commands
can be entered in the time programs. With this function, the domestic-hot-water circulation
pump can be switched on and off in a time-dependent pattern (with anti-jamming function).
+05
=
LP 2 is connected in series to LP 1 and charges the domestic-hot-water tank.
+06
=
Internal circulation pump (secondary; automatically regulated by controller).
+07
=
Contact is actuated in
and
operation of heating circuit 1, provided that UP 1 is
switched on. This signal can be connected to a pump-speed governor in order to reduce
pump speed during
and
operation (with activated frost protection).
+08
=
Contact is actuated in
and
operation of heating circuit 2, provided that UP 2 is
switched on. This signal can be connected to a pump-speed governor in order to reduce
pump speed during and
operation (with activated frost protection).
+09
=
Contact is actuated during the optimised warm-up phase of heating circuit 1.
+10
=
Contact is actuated during heat demand (for main primary pump or boiler pump)
SERV setting value
No.
Function
04
+3
Configuration of two-point output O
4
(terminal 7)
05
–1
Configuration of two-point output O
5
(terminal 6)
06
–1
Configuration of two-point output O
6
(terminal 4)
07
+1
Configuration of two-point output O
7
(terminal 3)
-1
+00
+01
+02
+03
+04
+05
+07
+08
+09
2
2
3
OPTEIN
0..
04
SERV..
04
0
07
0
06
05
06
5
7
5
N
0
4
L
7
5
N
0
5
L
6
5
N
0
6
L
4
5
N
0
7
L
3
+06
...
...
2
+10
B02640a
Mark the assigned function of the outputs and enter the value into the configuration sheet