SY6600 Vector Control Inverter User Manual
82
Fig.6-24 FAR and FAR detection width
P6.12 FDT1 level
Setting range: 0.0
~
400.0Hz
P6.13 FDT1 lag
Setting range: 0.0
~
10.00Hz
P6.14 FDT2 level
Setting range: 0.0
~
400.0Hz
P6.15 FDT2 lag
Setting range: 0.0
~
10.00Hz
If output frequency exceeds certain value, the terminal outputs indication
signal, and this signal is called FDT level.
If output frequency decreases, the terminal continues to outputs indication
signal, until the output frequency is lowered to the FDT signal width and exceeds
certain width, this width is called FDT signal lag, as shown in Fig.6-21 and 6-23.
P6.16 Preset value arriving
Setting range:0
~
9999
P6.17 Specified value arriving
Setting range:0
~
9999
For P6.16 and P6.17 function, please refer to definition of terminal function 13,
14.
P6.18 Terminal logic
Setting range:0
~
255