background image

SY6600 Vector Control Inverter      User Manual 

 

 

                                                               

  113

 

 

=0

reverse run 

bit1 

=1

inverter fault 

 

=0

inverter no fault 

bit2 

=1

inverter running   

=0

inverter stop 

bit3 

=1

data valid 

 

=0

data invalid 

bit4 

=1

RS485 frequency setting 

=0

local frequency setting 

BYTE8 

is the error code 

ED

 

End byte 

A0H

one byte 

SUM

 

Xor check 

Xor form BYTE1 

to

 BYTE9

 

     

3.2 Application note 

1.The OP,DT,ST,CON in communication protocol are two bytes. The address calculation of OP is 

converting the parameter address of the parameter list to HEX value. For example, 270 parameter, 

convert to 10E in hex format; the lower byte of OP is 0eh;the higher byte of OP is 01h. Other parameters 

that are not listed in parameter table are as following table. 

1000H 

Status word 

1001H 

Error code 

1002 H 

Control word 

1003H 

Frequency setting

 

1004H 

Running 

frequency

 

1005H 

Output current

 

1006H 

Output voltage

 

1007H 

DC bus voltage

 

1008H 

 

Overload rate

 

1009H 

Preset line speed

 

100AH 

Running 

line 

speed

 

100BH 

Output torque

 

100CH 

PI reference

 

100DH 

PI feedback

 

100EH 

reserved 

100FH 

Analog input AI1

 

1010H 

Analog 

input

 

AI2 

1011H 

I/O status

 

1012H 

External  counting 

value

 

1013H 

PID Set 

 

 

2

For example, the computer set the set frequency of the inverter to 50.00Hz and send the run command to the 

inverter. The address of the inverter is 01h. The OP of the setting frequency is 1003h in hex format. The Setting 

frequency 50.00(5000) is converted to 1388h in hex format. 

 

 

A message from computer to the inverter: 

02H 

01H 

10H 

03H 

10H 

88H 

13H 

03H 

00H 

A0H 

3AH 

 

The inverter response: 

02H 

01H 

00H 

03H 

10H 

88H 

13H 

1DH 

00H 

A0H 

34H 

3.3

 Fault and troubleshooting

 

1. The protocol provide 

Start byte, end byte , xor check means to ensure the correctness of the communication. 

 

2. There must be two bytes interval between two message. 

Summary of Contents for SY6600

Page 1: ...al Devices for Main Circuit 17 3 3 Lectotype of mMain Circuit Peripheral Devices 18 3 4 Product Terminal Configuration 18 3 5 Functions of Main Circuit Terminal 18 3 6 Attention for Main Circuit Wiring 20 3 7 Terminal Wiring 21 3 8 Functions of Control Circuit Terminals 22 3 9 Lectotype of Control Circuit Peripheral Devices 23 Chapter 4 Using Instructions of Operation Panel 24 4 1 Introduction to ...

Page 2: ...munication and Bus control function 95 Pd Faults and protection parameters 96 PE Factory reserved 99 PF Factory reserved 99 PH Display function 99 Chapter 7 Fault diagnosis and troubleshooting 102 7 1 Fault query at fault 102 7 2 List of Fault and Alarm Information 102 7 3 Troubleshooting Procedures 107 Chapter 8 Routine Repair and Maintenance 108 8 1 Routine Maintenance 108 8 2 Periodic Maintenan...

Page 3: ... class power class and software hardware versions SY6600 0R4 G 4 Inverter Series NO Inverter Type G Constant Torque Voltage No P Fan Water Pump 220V 2 380V 4 NO Adaptation 0R4G 0 4kw 0R7G 0 75KW 1R5G 1 5KW 2R2G 2 2KW 4R0G 4KW Fig 1 1 Inverter symbol description 1 2 Product Nameplate Description Fig 1 2 Inverter Nameplate Note The brake unit and RS485 communication unit are optional component if ne...

Page 4: ...erter failure may cause severe accident or loss safety measures such as redundancy or bypass shall be taken Goods Arrival Inspection Note Note If the inverter is found to be damaged or lack parts the inverter cannot be installed Otherwise accident may be caused Installation Note Note When handling and installing the product please hold the product bottom Do not hold the enclosure only Otherwise yo...

Page 5: ...t terminals U T1 V T2 and W T3 otherwise the inverter will be damaged It is forbidden to connect the output terminal of the inverter to the capacitor or LC RC noise filter with phase lead otherwise the internal components of the inverter may be damaged Please confirm that the power supply phases rated voltage are consistent with that of the nameplate otherwise the inverter may be damaged Do not pe...

Page 6: ... damaged The heatsink and the braking resistor have high temperature Please do not touch such device otherwise you may be burnt When it is used on lifting equipment mechanical contracting brake shall also be equipped Please do not change the inverter parameter randomly Most of the factory set parameters of the inverter can meet the operating requirement and the user only needs to set some necessar...

Page 7: ...nput Rated voltage frequen cy Three phase 380V 480V 50Hz 60Hz Allowable voltage range 323V 528V Voltage unbalanceness 3 allowable frequency fluctuation 5 Rated current A 3 5 6 2 9 2 14 9 Braking unit Built in as option Protection class IP20 Cooling mode Self cooling Forced air convection cooling SY6600 G 2 Three phase 200V Constant torque heavy duty application Power kW 0 4 0 75 1 5 2 2 Motor powe...

Page 8: ...ss Vector control V F control Running command input modes Panel control external terminal control control by serial port of host computer Speed setting mode Ten kinds of main frequency setting modes five kinds of Auxiliary frequency setting modes Several combination kinds of main frequency setting modes and Auxiliary frequency setting modes Speed setup resolution Digital setting 0 01Hz Analog sett...

Page 9: ...imit frequency starting frequency jump frequency frequency gain Carrier frequency adjustment Acc Dec mode selection voltage meter output current meter output multi frequency operation programming operation traverse operation PI close loop operation proportional control remote control FWD REV dead time etc Protection function Over voltage low voltage over current current limit overload over heat el...

Page 10: ...SY6600 Vector Control Inverter User Manual www sanyuacdrive com 键入文字 Cooling 0 75 kW and below enclosed self cooling Others forced cooling ...

Page 11: ...4 Fig 1 4 Product outline and mounting dimension 1 6 Product Outline Mounting Dimension and Weight Product outline mounting dimension and weight Voltage class Inverter model Outline and mounting dimension mm Approximate weight kg W H D W1 H1 D1 H2 Mounting hole diameter 220V SY6600 0R4G 2 0R7G 2 97 5 175 155 85 163 150 5 2 0 SY6600 1R5G 2 2R2G 2 400V SY6600 0R4G 4 2 0 SY6600 1R5G 4 SY6600 2R2G 4 S...

Page 12: ...e and mounting dimension 1 9 Braking Resistor Lectotype Inverter model Braking unit Braking resistor unit Braking torque Power Resis tor Qty SY6600 0R4G 2 opt ional 70W 200Ω 1 220 SY6600 0R7G 2 70W 200Ω 1 125 SY6600 1R5G 2 260W 100Ω 1 125 SY6600 2R2G 2 260W 70Ω 1 120 SY6600 0R7G 4 70W 750Ω 1 130 SY6600 1R5G 4 260W 400Ω 1 125 SY6600 2R2G 4 260W 250Ω 1 135 SY6600 004G 4 390W 150Ω 1 135 ...

Page 13: ... as wood Keep the drilling scraps from falling into the inside of inverter during the installation Mount the product vertically in the electric control cabinet mount the cooling fan or air conditioner to prevent the ambient temperature from rising to above 45 ºC For the sites with adverse environment it is recommended to mount the inverter heatsink outside the cabinet 2 2 Mounting Direction and Sp...

Page 14: ...align with the lower clamping position of the operation panel in direction 1 and then press down the operation panel in direction 2 until the crack sound is heard Do not mount the operation panel in any other direction otherwise the operation panel will have poor contact Fig 2 2 Removal of operation panel 2 3 2 Removal and Mounting of Covers of Inverter with Plastic Enclosure Removal of operation ...

Page 15: ...sert the upper claw grab on the lower cover into the groove of the upper cover as shown in position 1 of Fig 2 4 and then press the lower part of the lower cover in direction 2 of Fig 2 4 until the crack sound is heard Now tighten the cover screws Mounting of operation panel Please refer to 2 3 1 Removal and mounting of operation panel ...

Page 16: ...Product and Peripheral Devices Fig 3 1 Connection diagram of the product and peripheral devices Power supply Contactor Input AC reactor DC reactor Inverter Grounding Motor Grounding Circuit breaker or leakage circuit breaker Input noise filter Output noise filter Braking resistor Output AC reactor ...

Page 17: ... 4 It is required that the input power factor of the inverter shall be higher than 90 When the above situations occur install the AC reactor at the input end of the inverter or DC reactor to the DC reactor terminal Input noise filter The noise input from the power end to the inverter and output from the inverter to the power end can be reduced Thermal protection relay Although the inverter has mot...

Page 18: ...ver current protection and power failure maintenance the inverter shall connect to the power supply through the circuit breaker or leakage circuit breaker and contactor Please confirm that the power supply phases rated voltage are consistent with that of the nameplate otherwise the inverter may be damaged 3 6 2 Motor Wiring It is forbidden to short circuit or ground the inverter output terminal ot...

Page 19: ...It is suggested that when the motor cable is longer than 100m output AC reactor be installed Refer to the following table for the carrier frequency setting Length of cable between the inverter and motor Less than 50m Less than 100 m More than 100m Carrier frequency PA 00 Less than 15kHz Less than 10kHz Less than 5kHz 3 6 3 Grounding Wiring The inverter will produce leakage current The higher the c...

Page 20: ...l be grounded with 360 degree grounding method and sleeved into the metal tube The signal cable shall be kept far away from the inverter input wire and output motor wire If the signal cable must cross the input wire and output motor wire they shall be kept orthogonal When analog voltage and current signals are adopted for remote frequency setting twinning shielding cable shall be used The shieldin...

Page 21: ...SY6600 Vector Control Inverter User Manual 21 3 7 Terminal Wiring Fig 3 6 Terminal wiring diagram ...

Page 22: ...otection X1 X5 Multi functional input terminals 1 6 Input specification 24VDC 5mA Frequency range 0 200Hz Voltage range 24V 20 CM 24V grounding Internal isolated with GND Digital output Y1 Open collector output Voltage range 24V 20 maximum input current 50mA CM Open collector output common end Internal isolated with GND Analog input 10V Analog input reference voltage 10V 3 internal isolated with C...

Page 23: ...ess than 5kΩ Note 1 The arrangement sequence of the control circuit terminals is as follows 3 9 Lectotype of Control Circuit Peripheral Devices Terminal number Terminal screw Tightening torque N m Wire specification mm2 Wire type 10V AI1 AI2 485 485 AO1 GND M3 0 5 0 6 0 75 Twinning shielding cable 24V X1 X2 X3 X4 X5 CM Y1 CM A1 B1 C1 M3 0 5 0 6 0 75 Shielding cable ...

Page 24: ...mode indicator On Running command is given via operation panel Off Running command is given via terminals Flash Running command is given via host computer red RUN Running status indicator On Inverter is running Off Inverter has stopped Flash Inverter is stopping green F R Run forward indicator On In stop status inverter has run forward command In running status inverter is running forward Flash Ch...

Page 25: ...ve parameters value Increase Key 1 In first level menu increase function code PX according to edit bit 2 In second level menu increase the function code PX YZ data 3 In third level menu Increase the function code data Decrease 1 In first level menu decrease function code PX according to edit bit 2 In second level menu decrease the function PX YZ code data 3 In third level menu decrease the functio...

Page 26: ... 4 4 Fault alarm state In stopping running or programming state correspondent fault information will be reported if fault is detected At this time LED displays the fault code in flashing mode When fault alarm occurs press PRG key to enter programming menu and look up the fault log When fault alarm occurs the alarm picture is displayed and the fault can be reset by press STOP RESET key The drive re...

Page 27: ... second level menu directly but the parameters can not be saved and stop at current function code 4 5 2 Parameter setup Setting parameters correctly is a premise for actualizingSY6600 s performances Parameter setting method via panel will be introduced in the following part with rated power as an example Change 18 5kW into 7 5kW Operation process is shown in Fig 5 2 Press the SHIFT key with single...

Page 28: ...tate In stopping state the drive has 9 state parameters which can be scrolled by SHIFT key they are frequency setting external counting value digital value input terminal state digital value output terminal state panel potentiometer analog input AI1 analog input AI2 and DC bus voltage Please refer to the explanation of PH 01 The default value of PH 01 is preset frequency If PH 01 value is set to 2...

Page 29: ...g to the parameters on nameplate In order to get better control performance you can control the drive to perform auto tuning on the motor so as to get accurate motor parameters Parameter tuning can be done through P3 05 1 Set F0 01 parameter to 0 to select panel running command control mode 2 According the motor s name plat Set P3 00 P3 01 P3 02 P3 03 P3 04 parameter in proper order 3 Set P3 05 to...

Page 30: ...s please judge the fault causes and clear the fault according to 7 1 Fault and alarm information list If motor can without connecting the load rotating auto tuning can be selected P3 05 2 otherwise only static auto tuning can be selected When enabling the auto tuning please ensure the motor is in standstill status If over voltage or over current happens in auto tuning process you can prolong the a...

Page 31: ... code can be changed during operation This function code can only be changed during stopping status The setting of this function code is read only and cannot be changed 5 1 Function Parameter Table Function code Name Description Factory setting Order number Property P0 Group Basic parameter P0 00 reserved 0 P0 01 Running command selection 0 Keypad control 1 External terminal 2 Communication 0 1 P0...

Page 32: ... P0 07 Auxiliary frequency range selection 0 Maximum output frequency 1 Main frequency 0 7 P0 08 Auxiliary frequency range 0 100 100 8 P0 09 Setting Frequency selection 0 Main frequency 1 Auxiliary frequency 2 Main frequency Auxiliary frequency 3 Main frequency Auxiliary frequency 4 switch between Main frequency and Auxiliary frequency 5 switch between Main frequency and Main frequency Auxiliary f...

Page 33: ...on 1 Clear fault information 2 Recover factory setting Note After executing 1 2 steps restores to zero automatically 0 19 P1 Group Auxiliary function parameters 1 P1 00 Starting mode 0 Start from starting frequency 1 First braking then restart from starting frequency 0 20 P1 01 Starting frequency 0 50 20 00Hz 0 50 21 P1 02 Hold time of Starting Frequency 0 0 60 0s 0 22 P1 03 DC injection braking t...

Page 34: ...0 32 P1 13 Delay time for restarting after power failure 0 0 20 0s 2 0 33 P1 14 dynamic braking start voltage 630 710 660 34 P1 15 Rate of dynamic braking 0 No dynamic braking 1 100 90 35 P1 16 Action on frequency lower than lower frequency limit 0 dormancy 1 start running at lower frequency limit 2 Stop 0 36 P1 17 MF key function 0 No operation 1 reverse rotation 0 37 P1 18 Stop reset Key functio...

Page 35: ...Hz 0 00 53 P2 14 Multi frequency 6 0 00 400 0 Hz 0 00 54 P2 15 Multi frequency 7 0 00 400 0 Hz 0 00 55 P2 16 Multi frequency 8 0 00 400 0 Hz 0 00 56 P2 17 Multi frequency 9 0 00 400 0 Hz 0 00 57 P2 18 Multi frequency 10 0 00 400 0 Hz 0 00 58 P2 19 Multi frequency 11 0 00 400 0 Hz 0 00 59 P2 20 Multi frequency 12 0 00 400 0 Hz 0 00 60 P2 21 Multi frequency 13 0 00 400 0 Hz 0 00 61 P2 22 Multi frequ...

Page 36: ...rrent 0 1 999 9A Drive s rated value 76 P3 03 Motor rated frequency 1 00 400 0Hz 50 00 77 P3 04 Motor rated speed 1 9999RPM 1440 78 P3 05 Motor auto tuning 0 No operation 1 static auto tuning 2 overall auto tuning 0 79 P3 06 Stator resistance 0 001 20 00 Motor parameter 80 P3 07 Rotor resistance 0 001 20 00 Motor parameter 81 P3 08 Self inductance 1 000 9 999 Motor parameter 82 P3 09 Leakage induc...

Page 37: ...orque boost 0 0 20 0 base voltage 3 0 93 P4 08 Slip compensation 0 0 10 0 rated speed 0 00 94 P4 09 AVR function 0 disabled 1 enabled 0 95 P5 Group VC control P5 00 ASR proportional gain 1 0 000 6 000 2 000 96 P5 01 ASR integration time 1 0 000 9 999 0 500 97 P5 02 ASR proportional gain 2 0 000 6 000 1 000 98 P5 03 ASR integration time 2 0 000 9 999 1 000 99 P5 04 ASR switching frequency 00 00 99 ...

Page 38: ...11 Terminals for selecting Acc Dec time 2 12 Normally open terminal for inputting external fault 13 Normally close terminal for inputting external fault 14 Frequency increase command 15 Frequency decrease command 16 Free run to stop 17 Three wire control 18 switch of speed given mode 19 Reset terminal for program operation 20 Start traverse operation 21 pause traverse operation 22 DC braking comma...

Page 39: ...it frequency arriving 9 Overload signal 10 Over voltage stall 11 Over current stall 12 External stopping command 13 Preset counting value arriving 14 Specified counting value arriving 15 Low voltage lockup signal 16 Overload pre alarm 17 Drive failure signal 18 Zero speed running 19 end signal of stage of program operation 20 end signal of cycle of program operation 17 116 P6 10 Output terminal Y1...

Page 40: ...5 AI2 filter time 0 05 5 00s 0 50 131 P7 06 Minimum AI2 0 0 100 0 0 0 132 P7 07 Frequency corresponding to F7 11 0 00 100 0 Maximum output frequency 0 00 133 P7 08 Maximum AI2 0 0 100 0 100 0 134 P7 09 Frequency corresponding to F7 08 0 00 100 0 Maximum output frequency 100 0 135 P7 10 FWD REV dead time range 0 0 10 0 1 0 136 P7 11 AI1 filter time 0 05 5 00s 0 50 137 P7 12 Minimum AI0 0 0 100 0 0 ...

Page 41: ... 02 0 0 100 0 0 0 145 P8 04 Maximum AO1 0 0 100 0 100 0 146 P8 05 reserved 147 P8 06 reserved 148 P8 07 reserved 149 P8 08 reserved 150 P8 09 reserved 151 P9 Group program operating parameters P9 00 Programming operation function 0 Single cycle Stop after a single cycle 1 Continuous cycle 2 Maintain the final value 0 152 P9 01 Time Unit 0 Second 1 Minute 0 153 P9 02 Stage 1 timing T1 0 3600 0 0 15...

Page 42: ... 2 2 FWD Acc Dec time 3 3 FWD Acc Dec time 4 4 REV Acc Dec time 1 5 REV Acc Dec time 2 6 REV Acc Dec time 3 7 REV Acc Dec time 4 0 169 P9 18 T2 running mode 0 170 P9 19 T3 running mode 0 171 P9 20 T4 running mode 0 172 P9 21 T5 running mode 0 173 P9 22 T6 running mode 0 174 P9 23 T7 running mode 0 175 P9 24 T8 running mode 0 176 P9 25 T9 running mode 0 177 P9 26 T10 running mode 0 178 P9 27 T11 ru...

Page 43: ... 189 PA 05 Maximum reference 0 150 100 190 PA 06 Minimum feedback 0 100 0 191 PA 07 Maximum feedback 0 150 100 192 PA 08 Proportional gain 0 00 10 00 1 00 193 PA 09 Integration time 0 01 99 99s 0 5 194 PA 10 Differential time 0 00 no differentiation 0 01 99 99s 0 195 PA 11 Sample cycle 0 01 99 99s 0 1 196 PA 12 Error limit 0 0 15 0 0 0 197 PA 13 Level of abnormal feedback signal 0 100 50 198 PA 14...

Page 44: ... 0 00 400 0 Hz 0 00 209 Pb 04 Travers amplitude 0 0 50 0 Pb 03 0 0 210 Pb 05 Step frequency 0 0 50 0 Pb 04 0 0 211 Pb 06 Traverse cycle 0 1 999 9s 10 00 212 Pb 07 Rise time of triangular wave 0 0 100 0 Pb 06 50 0 213 PC Group 485 communication parameters PC 00 Baud rate selection 0 1200BPS 1 2400BPS 2 4800BPS 3 9600BPS 4 19200BPS 5 38400BPS 3 214 PC 01 Data format 0 8 N 2 for RTU MODBUS 1 8 E 1 fo...

Page 45: ...ection 1 220 Pd 01 Motor overload protection factor 20 0 150 0 100 0 221 Pd 02 Over voltage stall selection 0 Disabled 1 Enabled 1 222 Pd 03 Stall over voltage point 120 0 150 0 120 0 223 Pd 04 Selection of overload pre alarm detection 0 Detect at constant speed and alarm 1 Detect all the time and alarm 0 224 Pd 05 Overload detection threshold 20 0 180 0 150 0 225 Pd 06 Overload pre alarm delay 0 ...

Page 46: ...t selection at under voltage fault 0 No action 1 Act in running state 2 Act in running and stop state 1 233 Pd 14 reserved 234 Pd 15 reserved 235 Pd 16 reserved 236 Pd 17 reserved 237 Pd 18 reserved 238 Pd 19 reserved 239 Pd 20 reserved 240 PE Group group Reserve 1 PF group Reserve 2 PH Group Display parameters PH 00 running display parameters selection 0 Frequency setting 1 Running frequency 2 Ou...

Page 47: ...speed 2 DC Bus voltage 3 Analog input AI1 4 Analog input AI2 5 I O status 6 external counting value 7 PI reference 8 PI feedback 0 268 PH 02 Line speed factor 0 01 99 99 30 00 269 PH 03 Inverter Power 270 PH 04 Heatsink temperature 1 0 100 271 PH 05 Heatsink temperature 2 0 100 272 PH 06 1st fault type 273 PH 07 2nd fault type 274 PH 08 3rd fault type 275 PH 09 Bus voltage at last fault 276 PH 10 ...

Page 48: ...Inverter User Manual 48 last fault PH 12 Running frequency at last fault 279 PH 13 I O state at last fault 280 PH 14 Total operating time 281 PH 15 Software version of CPU Board 282 PH 16 Software version of Keypad Board 283 ...

Page 49: ...ing to get accurate parameters of motor After auto tuning motor parameters will be saved in the internal control board for control operation b To ensure high steady dynamic control performance user must set parameters of speed controller correctly For parameters setup and adjustment of speed controller please refer to explanation of P5 parameter group c If vector control mode is selected one SY660...

Page 50: ...set P9 parameter P0 04 Main Frequency gain Setting arrange 0 000 9 999 The main frequency is the product of the setting frequency selected by parameter P0 03 and this gain P0 05 Zero frequency source of multi speed mode Setting arrange 0 2 0 Panel potentiometer setting 0 5V 1 P0 11Digital frequency setting 1 External analog signal AI1 setting 2 External analog signal AI2 setting P0 06 Assit freque...

Page 51: ...ncy selection Setting range 0 9 Select the setting frequency source of the inverter 0 Main frequency The setting frequency source of the inverter is determined by the main frequency of the parameter of P0 03 1 Auxiliary frequency The setting frequency source of the inverter is determined by the auxiliary frequency of the parameter of P0 06 2 Main frequency Auxiliary frequency 3 Main frequency Auxi...

Page 52: ...de defined by function code Pb parameter group P0 10 up down setting store selection Setting range 0 1 0 Store The initial frequency setting value is the value of parameter P0 11 It can be changed by the terminal defined with function Frequency increase command and Frequency decrease command When the inverter is power off the current frequency setting value is stored 1 Not Store The initial freque...

Page 53: ...cy which the user is allowed to set shown in Fig 6 2 as FL Fb in Fig 6 2 is basic running frequency which is defined as the lowest output frequency when the inverter outputs the highest voltage in V F control mode Fig 6 2 Frequency limits definition P0 16 Acc time 1 Setting range 0 1 3600s P0 17 Dec time 1 Setting range 0 1 3600s Acc time means the time during which the inverter output from zero f...

Page 54: ...ng value is restored 3 Parameter locking When set P0 19 to 3 parameter locking function is enabled Except this parameter all other parameters are read only and can not be modified P1 Auxiliary function parameters 1 P1 00 start mode Setting range 0 2 0 Start from starting frequency When inverter begins running it starts from starting frequency P1 01 and runs for the preset time P1 02 at this freque...

Page 55: ... frequency is lower than the start frequency inverter s output frequency becomes zero Start frequency holding time the running time at start frequency in Acc Start process which is shown in Fig 6 4 P1 03 DC injection braking time at start Setting range 0 00 60 0s P1 04 injection braking current at start Setting range 0 0 100 0 inverter rated currente DC braking time at start holding time for outpu...

Page 56: ... frequency is decreased to zero If the running condition has no strict requirements for braking the initial frequency of DC injection braking should be set as low as possible P1 07 DC injection braking time Setting range 0 0 0 1 60 0s P1 08 DC injection braking current Setting range 0 0 100 0 inverter s rated current DC injection braking time the time for maintaining output DC injection braking in...

Page 57: ... Time of S curve s rising part Setting range 10 0 80 0 Acc Dec time The function codes of P1 10 and P1 11 define the Acc Dec parameters of S curve S curve start time is shown in Fig 6 6 as which is the stage when the slope of output frequency rises gradually S curve rise time is shown in Fig 6 6 as which is the stage when the slope of output frequency maintains phase S curve end time is shown in F...

Page 58: ... value if necessary P1 16 Start frequency lower than frequency limit Setting range 0 1 2 0 when preset frequency is lower than low frequency limit the inverter will not start 1 when preset frequency is lower than low frequency limit the inverter will start at low frequency limit 2 When preset frequency is lower than frequency limit the inverter stop P1 17 MF key function 0 No operation 1 reverse r...

Page 59: ...og Acc time P2 06 t3 is Jog Dec time P2 07 and t2 is the Jog running time Jog running command can be issued through panel control terminal or host computer Fig 6 7 Jog running parameters P2 09 Multi frequency 1 Setting range 0 400 0Hz P2 10 Multi frequency 2 Setting range 0 400 0Hz P2 11 Multi frequency 3 Setting range 0 400 0Hz P2 12 Multi frequency 4 Setting range 0 400 0Hz P2 13 Multi frequency...

Page 60: ...3 If multi frequency operation is selected Starting stopping the drive is determined by control mode selection P0 01 Freque ncy Termin al 1 X 2 X 3 X 4 X 5 X 6 X 7 X 8 X 9 X 10 X 11 X 12 X 13 X 14 X 15 X Termin al 1 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 Termin al 2 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 Termin al 3 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 Termin al 4 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 P2 24 Jump frequency 1 Setti...

Page 61: ... to change its rotating direction when the inverter receives REV command during its running process The time is shown in Fig 6 9 as T0 Fig 6 9 FWD REV dead time P2 29 REV prohibited Setting range 0 1 When P2 29 0 this function is disabled In this case terminal F R OFF Run FWD terminal F R ON Run Rev When P2 29 1 this function is enabled In this case terminal F R signal is invalid Motor can only ru...

Page 62: ...kage current increases and the wrong action of leakage protector and over current may happen Decreasing carrier frequency the contrary is the case Motor noise will increase in lower carrier frequency Influence of carrier frequency is different for various motors Therefore optimal carrier frequency should be selected according to practical situation In fact with the increase of motor capacity carri...

Page 63: ...s P3 00 Motor rated power Setting range 0 4 999 9kW P3 01 Motor rated voltage Setting range 0 440V P3 02 Motor rated current Setting range 0 1 999 9A P3 03 Motor rated frequency Setting range 1 00 400 0Hz P3 04 Motor rated speed Setting range 1 999 rpm Note In order to ensure motor tuning please set nameplate parameter of the motor correctly In order to ensure high control performance the motor ca...

Page 64: ... range 1 000 9 999 P3 09 leakage inductance Setting range 0 001 1 000 P3 11 Exciting current with no load Setting range 0 0 999 9A Factory settings of P3 06 F3 10 are the parameters of motor that rated power matches the inverter If user already knows the motor s parameters just input the motor parameters directly However after successfully performing motor auto tuning value of P3 06 P3 10 will be ...

Page 65: ...me special case it can be selected according to requirement In this condition both motor V F characteristic and output torque should be considered output Frequency output voltage UN 0 FMAX FBASE Fig 6 12 Base voltage and frequency P4 03 Intermediate voltage 1 Setting range 0 P4 04 P4 04 Intermediate voltage 2 Setting range P4 03 100 Inverter s rated voltage P4 05 Intermediate frequency 1 Setting r...

Page 66: ... AVR function Setting range 0 1 0 Disabled 1 Enabled AVR is auto voltage regulation When the inverter s input voltage differs with the rated input voltage the inverter s output voltage can be stabilized by adjusting the width of PWM wave This function is disabled when the output voltage is higher than input voltage P5 Vector control function P5 00 ASR proportional gain 1 Setting range 0 00 10 00 P...

Page 67: ...oscillation may occur given too big P Decreasing I will fasten transient response but system oscillation and overshoot may occur given too small Normally user may tune P first increase its value as long as no system oscillation occurs then adjust I ensuring fast response without overshoot Figure 6 15 shows better speed step response if P I are set properly Speed response can be monitored through a...

Page 68: ...djust ASR parameters following the procedures below 1 Set appropriate switching frequency P5 04 2 Tune proportional gain P5 00 and integration time P5 01 for low speed application and ensure no oscillation and good response performance at low frequency 3 Next tune proportional gain P5 02 and integration time P5 03 for high speed application and ensure no oscillation and good response performance a...

Page 69: ...0 0 200 0 motor s rated current Torque limiting is used to limit output torque current of speed regulator Torque limit is the percentage of the motor s rated current If the torque limit is 100 then the torque current limit is the motor s rated current P5 07 and P5 08 limit the output torque in driving state and braking state respectively which is shown in Figure 6 16 Fig 6 16 Torque limit function...

Page 70: ...op Fig 6 17 Two line control mode 1 In Fig 6 17 terminal X1 is defined as running FWD and X2 is defined as running REV 1 Two line operation mode 2 FWD REV Running command 0 0 Stop 0 1 Stop 1 0 FWD 1 1 REV Fig 6 18 Two line control mode 2 In Fig 8 18 terminal X1 is defined as running FWD and X2 is defined as running REV 2 Three wire operation mode 1 X1 FWD X2 REV COM K1 K2 X1 FWD X2 REV COM K1 K2 ...

Page 71: ...s for running the motor and they are active at pulse edge In Fig 6 19 and 8 20 Xi I 3 7 is defined as three wire running control terminal of X3 X7 In 3 wire mode when X3 X7 is not selected the inverter will report ERR4 fault P6 01 Up down rate Setting range 0 10 99 99Hz s Up down rate To define the increase decrease rate when using up down terminal to change reference frequency P6 02 Selecting the...

Page 72: ...s no function repeatedly that is it can be set as 0 at the same time Function description is shown below Content Function Content Function 0 X1 X5 No function can be selected repeatedly 16 Free run to stop 1 Run FWD 17 Three wire control 2 Run Rev 18 Voltage current switching 3 External reset 19 Input terminal for recording program operation 4 Jog FWD JOGF 20 Start traverse operation 5 Jog REV JOG...

Page 73: ...lect FWD REV operation 3 3 External RESET If fault alarm occurs user can reset the inverter by external terminal This function is active at rising edge of pulse signal It has the same function as STOP RESET key 4 4 5 Terminal for external FWD REV Jog running control In terminal control mode P0 01 1 this terminal is used to select Jog operation 5 6 9 Multi frequency terminals In multi frequency ope...

Page 74: ...he frequency setting value is increased or decreased at the rate defined by P6 01 when the terminal is OFF frequency setting value keeps constant When these two terminals are ON at the same time frequency setting value also keeps constant Please refer to P0 03 parameters description 9 16 Free run to stop terminal FRS When the function terminal is ON inverter stops output immediately and enter stop...

Page 75: ...rameters of DC injection braking time are invalid 14 23 Acc Dec disabled command When the terminal is ON the inverter temporarily inhibits executing the Acc Dec command and runs at current frequency When the terminal is OFF normal Acc Dec commands can be executed If there is any control signal with higher priority input such as external fault signal the inverter will exit Acc Dec inhibit state imm...

Page 76: ...operation state will not change if running command from external terminal is invalid the drive will stop running 16 25 Switch between panel control mode and external terminal control mode This function is used for selecting the physics channel that inputs inverter s running control command Selecting between keypad and external terminal to input control commands Commands input via external terminal...

Page 77: ...ID positive mode and negative mode When PA 00 is set to 0 PID positive mode is selected with the terminal is off negative models selected with the terminal is on 21 30 Emergence stop If the terminal defined with the function is on the inverter is in emergence stop status motor free stop P6 09 Programmable relay 1 Setting range 0 20 P6 10 Output terminal Y1 definition Setting range 0 20 Function se...

Page 78: ...t 1 1 Drive ready The drive is in normal waiting state and terminals output indication signal 2 2 Drive running signal l The drive is in running state and the terminal outputs indication signal 3 3 Drive running signal 2 In run status when the drive s output frequency is 0Hz the terminal does not output indication signal when the drive s output frequency is above 0Hz the terminal does output indic...

Page 79: ...cy reaches low limit frequency the terminal outputs indication signal 8 9 Overload signal When overload occurs the terminal outputs indication signal 9 10 Over current stall When over current stall occurs in running state terminal outputs indication signal 10 11 Over voltage stall When over voltage stall occurs in running state the terminal outputs indication signal 11 12 External stopping command...

Page 80: ...hen Xi inputs external counting pulse signal and the counting value reaches specified value defined by p6 17 See Fig 6 22 Y1 outputs an indication signal Y1 does not recover until specified value arrives As shown in Fig 6 22 if P6 16 5 P6 17 3 when Xi inputs the 3th pulse Y1 outputs an indication signal When Xi inputs the 5th pulse Y1 outputs specified value arriving signal Y1 will recover when th...

Page 81: ... start frequency when the inverter starts from zero frequency In Dec process output frequency is lower than initial frequency of DC injection braking 18 End signal of stage of program operation In program operation mode when a stage is finished the inverter outputs a pulse with width of 250ms 19 End signal of stage of program operation In program operation mode when a cycle is finished the inverte...

Page 82: ... indication signal and this signal is called FDT level If output frequency decreases the terminal continues to outputs indication signal until the output frequency is lowered to the FDT signal width and exceeds certain width this width is called FDT signal lag as shown in Fig 6 21 and 6 23 P6 16 Preset value arriving Setting range 0 9999 P6 17 Specified value arriving Setting range 0 9999 For P6 1...

Page 83: ...s output signal is valid In negative logic mode terminal Yi opens when its output signal is valid c Only decimal number can be set to the drive including display When negative logic is selected conversion from binary code to Hex value is shown as below Setting value 2 Y1 7 2 X6 5 2 X5 4 2 X4 3 2 X3 2 2 X2 1 X1 For example if X6 and X4 select negative logic and others are positive logic then Settin...

Page 84: ...pt that S1 AI2 is in I position P7 10 FWD REV dead time range Setting range 0 10 Maximum input signal If polarity control is selected P0 06 2 or 3 FWD REV dead time is set by this parameter Refer to parameter P0 06 and fig 6 1 for details P7 11 AI0 filter time Setting range 0 05 5 00S P7 12 Minimum AI0 0 0 100 0 P7 13 Frequency corresponding toP7 12 0 00 Maximum frequency P7 14 Maximum AI0 0 0 100...

Page 85: ...requency setting 0 Minimum F7 01 Hz Minimum value corresponding to the frequency F7 02 Input signal output frequency Maximum value F7 03 Maximum value corresponding to the frequency F7 04 Fig 6 26 curve 2 relationship between reference and frequency setting P8 Analog output terminal P8 00 AO1 output selection Setting range 0 9 P8 01 reserved Setting range 0 9 Inverter s state represented by analog...

Page 86: ...input AI2 0 10V p8 02 Minimum AO1 Setting range 0 00 100 0 p8 03 Minimum value corresponding to F8 02 Setting range 0 00 100 0 p8 04 Maximum AO1 Setting range 0 00 100 0 p8 05 Maximum value corresponding to F8 04 Setting range 0 00 100 0 This function code is used to setup maximum minimum value of analog output signal 0 10V and the relationship between these values and P8 00 is shown in Fig 6 27 a...

Page 87: ...F8 02 Corresponding to the minimum value F8 03 Maximum value F8 04 Corresponding to the maximum F8 05 Fig 6 28 Relationship between maximum minimum AO1 and F8 00 P9 Program operating parameters P9 parameter group is function code of programming operation Both programming operation and multi frequency operation are used for realizing the inverter s variable speed running according to certain regula...

Page 88: ...one cycle P9 01 Programming operation time setting unit Setting range 0 1 0 second 1 minute P9 02 Stage timing T1 Setting range 0 0 3600 0 P9 03 Stage timingT2 Setting range 0 0 3600 0 P9 04 Stage timing T3 Setting range 0 0 3600 0 P9 05 Stage timing T4 Setting range 0 0 3600 0 P9 06 Stage timing T5 Setting range 0 0 3600 0 P9 07 Stage timing T6 Setting range 0 0 3600 0 P9 08 Stage timingT7 Settin...

Page 89: ...ning mode Setting range 0 7 P9 23 T7Running mode Setting range 0 7 P9 24 T8Running mode Setting range 0 7 P9 25 T9Running mode Setting range 0 7 P9 26 T10Running mode Setting range 0 7 P9 27 T11Running mode Setting range 0 7 P9 28 T12Running mode Setting range 0 7 P9 29 T13Running mode Setting range 0 7 P9 30 T14Running mode Setting range 0 7 P9 31 T15Running mode Setting range 0 7 P9 17 P9 31 are...

Page 90: ...from the breakpoint When the drive stops user can clear counter value of current program by setting function code P9 00 again 2 Record function enabled In programming operation state program will pause when stop key is pressed Input running command again program will run from the breakpoint When the drive stops user can clear counter value of current program by setting function code P9 00 again PA...

Page 91: ...AI1 2 External analog signal AI2 3 Rs 485 communication setting 4 Panel potentiometer setting 0 5V PA 02 Feedback channel selection Setting range 0 1 1 External analog signal AI1 0 10V 2 Analog signal AI2 0 10V or 4 20mA PA 03 Digital setting of reference Setting range 0 00V 10 00V Digital reference is set by UP DOWN keypad PA 04Minimum referenc Setting range 0 0 100 0 PA 05 Maximum reference Sett...

Page 92: ...etting range of error limit then stop PID regulating PID regulator s output maintains constant PA 13 Level of abnormal feedback signal Setting range 0 100 This function code defines abnormal level of feedback signal Definition Abnormal level reference feedback reference 100 PA 14 Detection time of abnormal feedback signal Setting range 0 3600S This function code defines the detection time of abnor...

Page 93: ...equency delay time of waking and waking value Fig 6 30 PID sleeping and waking Pb Traverse function Pb 00 Traverse mode Setting range 0 1 0 Auto mode At first the drive operates at preset frequency of traverse operation Pb 01 for certain time Pb 02 and then enter traverse mode automatically 1 Manual mode If the multi function terminal Xi is set to terminal function 20 is enabled the drive will ent...

Page 94: ...ils Pb 03 Preset central frequency Setting range 0 00 400 0 Hz Traverse operation is shown in Fig 6 31 Pb 04 Travers amplitude Setting range 0 0 50 Travers amplitude Preset central frequency Fb 04 Pb 05 Step frequency Setting range 0 0 50 Refer to Fig 6 31 If it is set at 0 then there will be no step frequency Pb 06 Traverse cycle Setting range 0 1 999 9S It defines the period of traverse operatio...

Page 95: ...8 O 1 free communication format Pc 02 Local address Setting range 1 32 When the host is communicating with several inverters inverter s address is defined in this function code Pc 03 Communication timeout detect Setting range 0 0 0 1 100 0s The setting value is 0 No communication overtime protection The setting value isn t 0 in RS485 communication control mode if the communication between the inve...

Page 96: ...reshold of the electronic thermal overload relay overload current and current limit will be proportionally adjusted When motor capacity is lower than that of the drive this function is used provide overheat protection for the motor When several motors are driven by the same variable speed drive this function is disabled When display readings reaches 100 overload protection will be trigged Pd 02 Ov...

Page 97: ...Stall over voltage point 120 0 150 0 inverter s rated peak voltage Pd 04 Selection of overload pre alarm detection Setting range 0 1 0 Overload is only monitored during constant speed operation and alarms when overload occurs 1 Overload is monitored all the time and alarms when overload occurs Pd 05 Overload detection threshold Setting range 20 180 Pd 06 Overload pre alarm delay Setting range 0 60...

Page 98: ...y result in overvoltage protection The action mode of auto current limiting function is decided by PD 09 PD 09 0 disabled PD 09 1 auto current limiting is effective during acceleration or deceleration but ineffective at constant speed PD 09 2 auto current limiting is effective during acceleration deceleration and constant speed Pd 10 Auto reset Setting range 0 5 0 disabled 1 5 times of fault reset...

Page 99: ...ltage In some case when the input voltage is low or not stable the value can be adjusted to avoid under voltage fault PE Factory reserved PE 00 PE 05 are reserved parameters for individual consumer PF Factory reserved PF 00 PF 19 are reserved parameters for individual consumer PH Display function PH 00 running display parameters selection Setting range 0 14 SY6600 drive has 15 state parameters in ...

Page 100: ...rameters at stop Setting range 0 8 SY6600 drive has 9 state parameters in stopping state User can scroll through them by pressing key during stop state Function code PH 01 defines the default display parameter upon power on which includes 0 Frequency setting 1 Preset line speed 2 DC Bus voltage 3 Analog input AI1 4 Analog input AI2 5 I O status 6 external counting value 7 PI reference 8 PI feedbac...

Page 101: ...t in PH 09 PH 13 for checking Please refer to Chapter 7 for fault descriptions PH 09 Bus voltage at last fault V Setting range 0 999 PH 10 Output current at last fault A Setting range 0 999 9 PH 11 Frequency setting at last fault Hz Setting range 0 400 0 PH 12 Running frequency at last fault Hz Setting range 0 400 0 PH 13 I O state at last fault Setting range 0 511 PH 14 Total operating time Setti...

Page 102: ...e protection functions to provide efficient protection while utilizing its performance sufficiently Some failure instructions may be displayed during operation Compare the instructions with the following table and analyze decide the causes and solve failures For damages on units or questions that can t be resolved please contact with local distributors agents service centers or manufacturer for so...

Page 103: ...arameters properly Set start up frequency too high Decrease start up frequency Acceleration time is too short Lengthen acceleration time Set V F curve ratio too large Adjust V F curve setting and torque boost Power level of inverter is small Replace with inverter with proper model 5 occ2 Igbt module protection in Dec process Low grid voltage Check input power supply Rotating inertial of load is to...

Page 104: ...iation Blockage of air duct Clean the dusts wools and other foreign objects in the air duct Fan failure Check whether fan wirings are well connected Replace a new fan of the same model Inverter module failure Seek for technical support Temperature detection circuit failure Seek for technical support 18 oL1 Inverter overload protection Input power under voltage Check input power supply Fast start u...

Page 105: ...03 Keypad communication fault Keypad or its control line failure Check the connection of Keypad and its control line CPU failure Seek for technical support 25 ER04 Parameter setting failure In traverse or three wire operation mode wrong parameter setting Modify parameter setting 26 ER05 Communication abnormal 2 Terminal 485 The communication of terminal 485 is disconnected Check the connection of ...

Page 106: ...andard parameters Executed motor auto tuning again under zero load condition 30 ER09 Current detection failure Current sensor failure and bad contact Check the current sensor 32 END Trial period is outdated Contact your supplier Contact your supplier 33 ER12 External fault Act trigger by external fault Check external device according external fault signal 34 OL Overload pre alarm 1 Refer to OL1 an...

Page 107: ...SY6600 Vector Control Inverter User Manual 107 7 3 Troubleshooting Procedures ...

Page 108: ...l be conducted as per the table below Item Inspection Contents Inspection Means Criteria Operating Environment Temperature Thermometer 10 40ºC Derated at 40 to 50ºC and the rated output current shall be decreased by 1 for every temperature rise of 1ºC Humidity Humidiometer 5 95 no condensing Dust oil water and drop Visual check There are no dust oil water and drop Vibration Special test instrument...

Page 109: ...al check There are no foreign objects Motor Insulation test 500VDC megameter Normal 8 3 Component Replacement Different types of components have different service lives The service lives of the components are subject to the environment and application conditions Better working environment may prolong the service lives of the components The cooling fan and electrolytic capacitor are vulnerable comp...

Page 110: ...t 0 8 N 2 for RTU MODBUS Default 1 8 E 1 for RTU MODBUS 2 8 O 1 for RTU MODBUS 3 7 N 2 for ASCII MODBUS 4 7 E 1 for ASCII MODBUS 5 7 O 1 for ASCII MODBUS 6 8 N 1 free communication format 7 8 E 1 free communication format 8 8 O 1 free communication format 2 2 Baud rate Available baud rate 1200 2400 4800 9600 19200 38400 115200 The default value is 9600 BPS 2 3 Communication address Slave address r...

Page 111: ...ty 8 O 1 8 bit data one bit stop Odd parity 1 A message from computer to inverter BYTE0 BYTE1 BYTE2 BYTE3 BYTE4 BYTE5 BYTE6 BYTE7 BYTE8 BYTE9 BYTE10 HD AD CD OP DT CON ED SUM Item Byte Name Detail HD Start byte 02H one byte AD address Inverter address one byte 0 is broadcast address CD Parameter R W command One byte 0h no operation 1h read parameter from the inverter 10h write parameter from the i...

Page 112: ...TE10 HD AD CT OP DT ST ED SUM Item Byte name Detail HD Start byte 02H one byte IN address Inverter address one byte 0 is broadcast address CT Parameter operation status One bye 0 success 1 data received is exceed the range 2 address is exceed the range 3 data can not be modified while inverter is running 4 data is read only can not be modified OP Parameter number Parameter number two bytes BYTE3 i...

Page 113: ...cy setting 1004H Running frequency 1005H Output current 1006H Output voltage 1007H DC bus voltage 1008H Overload rate 1009H Preset line speed 100AH Running line speed 100BH Output torque 100CH PI reference 100DH PI feedback 100EH reserved 100FH Analog input AI1 1010H Analog input AI2 1011H I O status 1012H External counting value 1013H PID Set 2 For example the computer set the set frequency of th...

Page 114: ...adecimal system and the valid ASCII characters are 0 9 A F which is expressed in hexadecimal format Such as ASCII character 0 1 2 3 4 5 6 7 8 9 A B C D E F ASCII code Hex 30H 31H 32H 33H 34H 35H 36H 37H 38H 39H 41H 42H 43H 44H 45H 46H 7 N 2 start 0 1 2 3 4 5 6 stop stop 7 E 1 start 0 1 2 3 4 5 6 even stop 7 O 1 start 0 1 2 3 4 5 6 odd stop 2 RTU 8 N 2 start 0 1 2 3 4 5 6 7 stop stop 8 E 1 start 0 ...

Page 115: ...age format of master request Slave address Function code Start address of data Data quantity Unit word Redundanc y check 1 byte 03H MSB LSB MSB LSB LS B MSB Message format of slave response Slave address Function code Data quantity Data 1 Data n Redundancy check 1 byte 03H 1 byte MSB LSB MSB LSB LSB MSB MSB high byte of double byte number LSB low byte of double byte number 2 Modify data Message fo...

Page 116: ...ive is normal After receiving data content the drive will return it to main control equipment without any modifying ASCII 1 Read data Reading data should be less than 30 bytes at a time Message format of master request Fram e head Slave address Functio n code Data address Data quantity LRC Frame tail MS B LS B 0 3 4 3 2 1 4 3 2 1 MS B LS B C R L F Message format of slave response Fram e head Slave...

Page 117: ... response Fram e head Slave address Functio n code Data address Modified value LRC Frame tail MS B LS B 0 6 4 3 2 1 4 3 2 1 MS B LS B C R L F 3 Examples 1 Function code 03H Read parameter data ASCII mode Format of query message Format of response message Starting character Starting character Slave address 0 Slave address 0 1 1 Function code 0 Function code 0 3 3 Data address 0 Data address 0 2 0 0...

Page 118: ...nction code 03H Data address 02H Data address 00H 00H 02H Data quantity Word 00H Data content 15H 01H 59H Low byte CRC 85H Low byte CRC 2AH High byte CRC B2H High byte CRC A0H 2 Function code 06H Write parameter data ASCII mode Format of query message Format of response message Starting character Starting character Slave address 0 Slave address 0 1 1 Function code 0 Function code 0 6 6 Data addres...

Page 119: ...ge Slave address 01H Slave address 01H Function code 06H Function code 06H Data address 01H Data address 01H 00H 00H Modified value 17H Modified value 17H 70H 70H Low byte CRC 86H Low byte CRC 86H High byte CRC 22H High byte CRC 22H 3 Function code 08H loop detection ASCII mode Format of query message Format of response message Starting character Starting character Slave address 0 Slave address 0 ...

Page 120: ...D CR END CR LF LF RTU mode Format of query message Format of response message Slave address 01H Slave address 01H Function code 08H Function code 08H Sub function code 00H Sub function code 00H 00H 00H Data content 12H Data content 12H ABH ABH Low byte CRC ADH Low byte CRC ADH High byte CRC 14H High byte CRC 14H 4 4 Control word and status word 1 Information of status word 2 bytes 2000H Bit0 1 FWD...

Page 121: ...5 1 RS485 running control 0 Local running control 2 Information of status word 2 bytes 2002H Bit0 1 Running command 0 No running command Bit1 1 FWD 0 REV Bit2 1 Jog FWD 0 Jog FWD and stop Bit3 1 Jog REV 0 Jog REV and stop Bit4 1 Fault reset command 0 No fault reset command Bit5 1 Host computer control valid 0 Host computer control invalid Bit6 1 Free run to stop 0 No free run to stop Bit7 1 Dec to...

Page 122: ...Running line speed 100BH Output torque 100C H PI reference 100D H PI feedback 100EH reserved 100FH Analog input AI1 1010 H Analog input AI2 1011H I O status 1012H External counting value 1013 H PID close loop setting 4 5 Fault and troubleshooting If communication fault occurs the drive will response fault code and report function code or 80H to the main control equipment For example ASCII mode RTU...

Page 123: ...mand 09 Wrong CRC check 11 Reserved 12 Message characters of the command string is too short 13 Command string is too long and reading string should be less than 72 characters 14 Contains non ASCII character non starting character or non CR LF end character Additional information 1 Function code conversion If preset data is n then sending data n n 1 increment Refer to function parameters table Con...

Page 124: ...e CRC register one bit to the right toward the LSB and fill the MSB with 0 Step 4 If the shifted bit is 0 save the new value of step 3 to CRC register otherwise execute XOR operation with A001H and CRC register and save the result in CRC register Step 5 Repeat step3 4 until 8 shifts have been performed Step 6 Repeat step2 5 for the next 8 bit message command Continue doing this until all messages ...

Page 125: ...r Manual 125 Appendix B Control Mode Setting Process A inverter connected to a computer Appendix Fig 1 A inverter connected to a computer Several inverters connected to a computer Appendix Fig 2 Several inverters connected to a computer ...

Reviews: