SY6600 Vector Control Inverter User Manual
30
4.8 Running for the First Time
Please follow the procedures to run the inverter for the first time:
P7.10 P7.10
50Hz
FWD
50Hz
REV
5V
10V
AI1
AI2
P7.01=50% P7.02=0Hz
P7.06=50% P7.07=0Hz
OR
Note
:
◆
If fault happens, please judge the fault
causes and clear the fault according to
7.1 Fault and alarm information list.
◆
If motor can without connecting the load
rotating auto tuning can be selected
(P3.05=2),otherwise only static auto
tuning can be selected .When enabling
the auto tuning please ensure the motor is
in standstill status .If over voltage or over
current happens in auto tuning process,
you can prolong the acceleration and
deceleration times of P0.16 and P0.17.