SY6600 Vector Control Inverter User Manual
53
。
P0.13 Maximum output
frequency
Setting range: 50Hz
~
400.0Hz
P0.14 High frequency limit
Setting range: lower frequency limit ~ Maximum output
frequency
P0.15 Low frequency limit
Setting range: 0.00Hz
~
Upper frequency limit
The maximum output frequency is the maximum frequency which the inverter is able to
output, shown in Fig. 6-2 as Fmax;
High frequency limit is the maximum frequency which the user is allowed to set, shown in
Fig. 6-2 as Fh;
Low frequency limit is the minimum frequency which the user is allowed to set, shown in
Fig. 6-2 as FL;
Fb in Fig.6-2 is basic running frequency, which is defined as the lowest output frequency
when the inverter outputs the highest voltage in V/F control mode.
Fig.6-2 Frequency limits definition
P0.16 Acc time 1
Setting range: 0.1
~
3600s
P0.17 Dec time 1
Setting range: 0.1
~
3600s
Acc time means the time during which the inverter output from zero frequency to the
maximum output frequency, shown in Fig. 6-3 as T1.
Dec time means the time during which the inverter outputs from the maximum output
frequency to zero frequency, shown in Fig. 6-3 as T2.
Fmax
Time
output frequency
T2
T1
Fig 6-3 Definition of Acc/Dec tim
Factory setting of Acc/Dec time: Acc/Dec time 1
(
P0.16
、
P0.17
)
。