(3) Check remote control unit.
(4) Check fuse on the indoor P.C.Board.
(5) Check TIMER on the remote control unit.
Yes
First remote control unit is defective.
No
No
Measure resistance of indoor and
outdoor fan motor (FM) winding.
Measure resistance of compressor
motor (CM) winding.
Replace the fuse.
Yes
Yes
Cancel the timer mode.
ON
1. Try to run with another remote
control unit.
2. Is the operation good ?
In the case that the remote control
transmission section is dirty, clean it.
In the case that the remote control
reception section in front of indoor unit
is dirty, clean it.
1. Is timer turned ON ?
2. Is displayed on remote control ?
1. Check fuse (F) on indoor P.C.Board
for continuity.
2. Is fuse blown ?
Is operation lamp ON ?
Indoor P.C.Board is defective.
57
Summary of Contents for 1 852 351 85
Page 2: ...SANYO Electric Co Ltd Jul 2009 R D center ...
Page 18: ...3 DIMENSIONAL DATA Indoor Unit SAP K77GHAX SAP K97GHAX SAP K127GHAX 16 ...
Page 83: ...SANYO Electric Co Ltd Jul 2009 R D center ...
Page 92: ......
Page 93: ......
Page 94: ......
Page 95: ......
Page 96: ......
Page 97: ......
Page 99: ...3 DIMENSIONAL DATA Indoor Unit SAP K77GHAX SAP K97GHAX SAP K127GHAX 16 ...
Page 113: ......
Page 123: ......
Page 124: ......
Page 125: ......
Page 136: ...C 53 ON 1 ...
Page 137: ......
Page 146: ......
Page 149: ......
Page 150: ......
Page 151: ......
Page 152: ......
Page 153: ......
Page 154: ......
Page 155: ......
Page 156: ......
Page 157: ......
Page 158: ......
Page 159: ......
Page 160: ......
Page 161: ......
Page 162: ......
Page 163: ......