9-3-1. Only indoor fan does not run.
9-3-2. Only flap motor does not run.
9-3-3. Only outdoor fan does not run.
9-3. Some part of air conditioner does not operate.
No
Yes
If you turn fan gently once or twice
by hand, can the fan turn ?
Check fan casing
foreign matter on
inside.
Fan motor winding
burnout or foreign
matter in bearings.
Remove foreign
matter or repair.
Repair or replace.
• Check fan motor capacitor.
Check fan motor capacitor.
No
When fan speed is changed, does
applied voltage between lead wires
BRN and WHT change as well ?
P.C.Board is defective.
Check connectors to P.C.Board.
Measure resistance of flap motor
winding and check the connector.
No
If you turn fan gently once or twice
by hand, can the fan turn ?
Check fan casing
foreign matter on
inside.
Fan motor winding
burnout or foreign
matter in bearings.
Remove foreign
matter or repair.
Repair or replace.
Yes
Check fan motor capacitor.
Check connectors to indoor unit
P.C.Board.
Check connectors to outdoor fan
motor lead wires.
1. Measure resistance of indoor fan
motor winding.
2. Is the resistance OK ?
1. Measure resistance of outdoor fan
motor winding.
2. Is the resistance OK ?
59
Summary of Contents for 1 852 351 85
Page 2: ...SANYO Electric Co Ltd Jul 2009 R D center ...
Page 18: ...3 DIMENSIONAL DATA Indoor Unit SAP K77GHAX SAP K97GHAX SAP K127GHAX 16 ...
Page 83: ...SANYO Electric Co Ltd Jul 2009 R D center ...
Page 92: ......
Page 93: ......
Page 94: ......
Page 95: ......
Page 96: ......
Page 97: ......
Page 99: ...3 DIMENSIONAL DATA Indoor Unit SAP K77GHAX SAP K97GHAX SAP K127GHAX 16 ...
Page 113: ......
Page 123: ......
Page 124: ......
Page 125: ......
Page 136: ...C 53 ON 1 ...
Page 137: ......
Page 146: ......
Page 149: ......
Page 150: ......
Page 151: ......
Page 152: ......
Page 153: ......
Page 154: ......
Page 155: ......
Page 156: ......
Page 157: ......
Page 158: ......
Page 159: ......
Page 160: ......
Page 161: ......
Page 162: ......
Page 163: ......