8-2. Dry Operation (Dehumidification)
Dry operation uses the ability of the cooling cycle to remove moisture from the air, but by running at low level to
dehumidify without greatly reducing the room temperature. The air conditioner repeats the cycle of turning ON
and OFF automatically as shown in the chart below according to the room temperature.
NOTE
< Cooling operation >
T+2 C
T-1 C
T+1 C
< Monitor zone >
Room temp. 15 C
T-1 C
T C
Room temp. 15 C
< Dry A zone >
Compressor :
FMI (indoor fan) :
Continuous operation
Indoor fan operates with rhythm airflow.
< Dry B zone >
Compressor :
FMI (indoor fan) :
Intermittent operation
(ON for 3 minutes and OFF for 9 minutes)
Indoor fan operates with rhythm airflow.
When room temp.
goes down
When room temp.
goes up
T : Set temp.
The air conditioner operates in cooling mode.
Both the indoor and outdoor units stop.
Intermittent ventilation occurs by switching the indoor fan speed between L and LL.
DRY operation does not occur when the room temperature is 15 C or less, which is the monitor zone.
When the compressor stops, the indoor fan stops as well.
46
Summary of Contents for 1 852 351 85
Page 2: ...SANYO Electric Co Ltd Jul 2009 R D center ...
Page 18: ...3 DIMENSIONAL DATA Indoor Unit SAP K77GHAX SAP K97GHAX SAP K127GHAX 16 ...
Page 83: ...SANYO Electric Co Ltd Jul 2009 R D center ...
Page 92: ......
Page 93: ......
Page 94: ......
Page 95: ......
Page 96: ......
Page 97: ......
Page 99: ...3 DIMENSIONAL DATA Indoor Unit SAP K77GHAX SAP K97GHAX SAP K127GHAX 16 ...
Page 113: ......
Page 123: ......
Page 124: ......
Page 125: ......
Page 136: ...C 53 ON 1 ...
Page 137: ......
Page 146: ......
Page 149: ......
Page 150: ......
Page 151: ......
Page 152: ......
Page 153: ......
Page 154: ......
Page 155: ......
Page 156: ......
Page 157: ......
Page 158: ......
Page 159: ......
Page 160: ......
Page 161: ......
Page 162: ......
Page 163: ......