8. FUNCTIONS
8-1. Room Temperature Control
(1) Cooling
Room temperature control is obtained by cycling the compressor ON and OFF under control of the room
temperature sensor in the indoor unit.
Once the compressor starts, it keeps running for 5 minutes.
Once the compressor stops, it will not start running again for 3 minutes.
Thermo. ON :
When room temperature rises 1 C above the set temperature T C,
the compressor turns ON.
Thermo. OFF : When the room temperature falls below the set temperature T C,
the compressor turns OFF.
ON
OFF
ON
OFF
ON
OFF
Compressor
ON
OFF
ON
OFF
ON
OFF
Outdoor fan
T+1 C
T
C
Set temp.
Thermo.
OFF
Thermo.
OFF
Thermo.
OFF
Thermo.
ON
Thermo.
ON
Room temp.
NOTE
Some informations except for the room temperature are transmitted every 5 minutes
by the remote control unit to the controller in the indoor unit.
44
Summary of Contents for 1 852 351 85
Page 2: ...SANYO Electric Co Ltd Jul 2009 R D center ...
Page 18: ...3 DIMENSIONAL DATA Indoor Unit SAP K77GHAX SAP K97GHAX SAP K127GHAX 16 ...
Page 83: ...SANYO Electric Co Ltd Jul 2009 R D center ...
Page 92: ......
Page 93: ......
Page 94: ......
Page 95: ......
Page 96: ......
Page 97: ......
Page 99: ...3 DIMENSIONAL DATA Indoor Unit SAP K77GHAX SAP K97GHAX SAP K127GHAX 16 ...
Page 113: ......
Page 123: ......
Page 124: ......
Page 125: ......
Page 136: ...C 53 ON 1 ...
Page 137: ......
Page 146: ......
Page 149: ......
Page 150: ......
Page 151: ......
Page 152: ......
Page 153: ......
Page 154: ......
Page 155: ......
Page 156: ......
Page 157: ......
Page 158: ......
Page 159: ......
Page 160: ......
Page 161: ......
Page 162: ......
Page 163: ......