(2) Circuit breaker trips in several minutes after turning the air conditioner on.
There is a possibility of short circuit.
Replace with suitable
one (larger capacity).
No
Measure resistance of outdoor fan
motor winding.
Measure resistance of compressor
motor winding.
Measure resistance of 4-way valve's
winding.
In case of Heating operation :
9-2-2. Neither indoor nor outdoor unit runs.
(1) Power is not supplied.
No
Circuit breaker
is tripped.
Power failure
Reset breaker.
Wait for recovery
or contact power
company.
1. Check capacity of circuit breaker.
2. Is capacity of circuit breaker
suitable ?
1. Check power supply.
2. Is power being supplied to the outdoor
unit ?
56
(2) Check "OPERATION lamp" in the indoor unit.
Alarm Signal (*)
Operation lamp on the front side of the indoor unit will flash on and off when either of indoor room thermistor,
coil thermistor and indoor fan motor is defective.
NOTE
• Operation lamp on front side of
indoor unit is flashing on and off. (*)
YES
• Replace thermistor.
• Indoor room thermistor and/or coil
thermistor is defective.
YES
Summary of Contents for 1 852 351 85
Page 2: ...SANYO Electric Co Ltd Jul 2009 R D center ...
Page 18: ...3 DIMENSIONAL DATA Indoor Unit SAP K77GHAX SAP K97GHAX SAP K127GHAX 16 ...
Page 83: ...SANYO Electric Co Ltd Jul 2009 R D center ...
Page 92: ......
Page 93: ......
Page 94: ......
Page 95: ......
Page 96: ......
Page 97: ......
Page 99: ...3 DIMENSIONAL DATA Indoor Unit SAP K77GHAX SAP K97GHAX SAP K127GHAX 16 ...
Page 113: ......
Page 123: ......
Page 124: ......
Page 125: ......
Page 136: ...C 53 ON 1 ...
Page 137: ......
Page 146: ......
Page 149: ......
Page 150: ......
Page 151: ......
Page 152: ......
Page 153: ......
Page 154: ......
Page 155: ......
Page 156: ......
Page 157: ......
Page 158: ......
Page 159: ......
Page 160: ......
Page 161: ......
Page 162: ......
Page 163: ......