9-4-1. Poor cooling.
9-4-2. Excessive cooling.
No
Yes
Yes
Yes
If temperature difference
is small, possibility of
gas shortage.
No
Change position of remote
control unit.
Are wide and narrow tubes between
indoor unit and outdoor unit
insulated ?
Insulate both wide and narrow
tubes separately and then
tape together.
Measure temperature of suction and
discharge air of air conditioner.
Check for clogging of air filter.
Is fan speed set to LOW ?
Set fan speed to either
HIGH or MEDIUM.
If performance of air conditioner is
normal, review cooling load estimate.
Reduce cooling load or
replace the air conditioner
with larger capacity.
No
No
Is set temperature suitable ?
Set temperature to higher
value using temperature
setting buttons of the remote
control unit.
Is remote control unit placed where
it can detect room temperature
properly ?
Is remote control unit placed where
it can detect room temperature
properly ?
Change position of remote
control unit.
Is temperature difference between
suction and discharge air large enough ?
(approx. 10 deg. or more).
If air filter is clogged,
clean the filter.
9-4. Air conditioner operates, but abnormalities are observed.
Charge refrigerant
gas (R22).
61
Summary of Contents for 1 852 351 85
Page 2: ...SANYO Electric Co Ltd Jul 2009 R D center ...
Page 18: ...3 DIMENSIONAL DATA Indoor Unit SAP K77GHAX SAP K97GHAX SAP K127GHAX 16 ...
Page 83: ...SANYO Electric Co Ltd Jul 2009 R D center ...
Page 92: ......
Page 93: ......
Page 94: ......
Page 95: ......
Page 96: ......
Page 97: ......
Page 99: ...3 DIMENSIONAL DATA Indoor Unit SAP K77GHAX SAP K97GHAX SAP K127GHAX 16 ...
Page 113: ......
Page 123: ......
Page 124: ......
Page 125: ......
Page 136: ...C 53 ON 1 ...
Page 137: ......
Page 146: ......
Page 149: ......
Page 150: ......
Page 151: ......
Page 152: ......
Page 153: ......
Page 154: ......
Page 155: ......
Page 156: ......
Page 157: ......
Page 158: ......
Page 159: ......
Page 160: ......
Page 161: ......
Page 162: ......
Page 163: ......