From the LCD panel, you can use the CONTROL menu to start or stop the UPS system. When you perform this operation,
the entire UPS system starts or stops. It is not possible to use this operation to start or stop individual UPS units. Before
stopping the UPS system, be sure to stop the load devices first.
①
Press
to display the LCD screen.
②
Press
to change the home menu to the one shown below.
③
Press
to accept it.
④
In the same way, follow the figure below to make selection at each level, as follows:
“Home menu”
→
“Operation” and continue
⑤
Use
to switch items, and then press
to select a desired item. When the confirmation screen appears, press
to perform the operation.
⑥
Press
to return to the home menu.
Operation
Home menu
STATUS
MEASUREMENT
MAINTENANCE
CONTROL
INV OFF
1
2
3
STATUS
Example: Stopping UPS
*1. Pressing
repeatedly cycles through the
displayed items. If you miss a desired item, just
keep on pressing until you see it again.
*2. To return to the previous level, press
.
*3. If
Wait・・・
appears, use
to go back and try
again. If the operation still fails, contact your
supplier or SANYO DENKI.
SETTING
BYPASS
CONTROL
[SELECT] = OK
[BACK] = Cancel
Confirm
INV OFF
Control OK
If
OK
: Screen switches in about 1 second
IF UPS is running,
INV OFF
appears.
If UPS stops,
INV ON
appeasrs.
INV OFF
Control NG
If
NG
: UPS is in a state where it cannot
start or stop. Screen switches in about 3
seconds later.
The operations are not possible in the following cases.
UPS cannot start when:
①
Inverter is starting up.
②
Input voltage and input frequency exceed
rated range
③
UPS is malfunctioning
UPS cannot stop when:
①
During bypass operation
②
Inverter stops
You can also use the
button on the LCD panel or the
button on the main unit's control panel
to start or stop the UPS. For details, refer to “Performing Operation” in the
A11J Instruction Manual.
C O N T R O L
B A T T E R Y T E S T
CONTROL
INV OFF
- STANDBY
–
Vi= V Fi= Hz
④
During continuous input of
Remote OFF
signal
⑤
During EPO signal input
⑥
Forced bypass switch
Forced Bypass
is on “Bypass” side.
Note on starting or stopping UPS
Starting or stopping UPS with ON/OFF button
Tip
*1
*2
*3