This section describes how to specify the number of UPS units in parallel connection to form a UPS system.
Because this value has been set at the factory, normally do not change it.
①
Press
to display the LCD screen.
②
Press
to change the home menu to the one shown below.
③
Press
to accept it.
④
In the same way, follow the figure below to make selection at each level, as follows:
“Home menu”
→
“Setting group”
→
“Setting”
→
“Value”
⑤
Use
to switch values, and then press
to select a desired value. When the confirmation screen appears, press
again to accept the value.
⑥
Press
to return to the home menu.
*1. Pressing
repeatedly cycles through the
displayed items. If you miss a desired item,
just keep on pressing until you see it again.
*2. To return to the previous level, press
.
*3. When you switch to the values screen, the
value shown is the current value, which is
indicated by “
> >
” .
*4. When a value has been changed and accepted,
it is indicated by “
>>
” (current value).
Settings group
Settings
Home menu
STATUS
MEASUREMENT
SETTING
MAINTENANCE
CONTROL
SET I/F
ChA Total Unit#
>> 1
Values
2
1
2
3
Details on settings and values
Value
Description
1
One UPS unit is used.
The default is
different depending
on the UPS model.
2
2 UPS units are connected.
3
3 UPS units are connected.
4
4 UPS units are connected.
5
5 UPS units are connected.
6
6 UPS units are connected.
7
7 UPS units are connected.
8
8 UPS units are connected.
[SELECT] = OK
[BACK] = Cancel
STATUS
Example: Set the number of UPS units to “
3
”
Confirm
Accept
S E T T I N G
SET IN/OUT
ChA Total Unit#
3
4
5
SET OPERATION
SET BATTERY
ChA Total Unit#
>> 3
7
6
SET FUNCTION
SETTING
SET SYSTEM
SET SYSTEM
ChA Total Unit#
Redundancy
INPUT Phases
SET SYSTEM
DATE/TIME
8
SET DEFAULT
ChB Total Unit#
ChB Total Unit#
has a value of
1
. Do not
change it. If you have changed the value by
mistake, select
ChB Total Unit#
and then
use the same procedure to change its value.
Note
*1
Tip
*2
*3
*4
If you have added a UPS unit or changed the number of UPS units connected, change this setting
to match the number of UPS units actually connected. If a UPS unit stops during operation for
some reason so that the number of operating UPS units does not match the setting, the message
“
Total Unit# Err
” appears in the UPS status display on the LCD panel.
After you perform the operation in §3.22 “Resetting Values of Settings”, this setting returns to
1
.
In this case, check the number of UPS units in the system and then change the setting again.