7
Settings group
Settings
Values
Default
setting
Current
setting
Ref
item
Ref
page
Display
Description
Display
Description
S E T F U N C T I O N
(Function Setting)
RUN TIM @PF
Operating
period during
outage
Set the time from
when UPS starts
backup to when it
stops output.
BATT END
Until end of battery
discharge
*
3.15 22
10 Sec.
Stop output after 10
seconds
30 Sec.
Stop output after 30
seconds
1 Min.
Stop output after 1
minute
3 Min.
Stop output after 3
minutes
5 Min.
Stop output after 5
minutes
10 Min.
Stop output after 10
minutes
RING Output
RING operation
Set whether to output
RING signal during
UPS startup.
Output
Output
3.16 23
None
Do not output
*
Out Vol Adj.
Output voltage
adjustment
Set value adjustment
for rated voltage set
in 3.1.
Each increment of
adjustment is about
1V
-3
Minus 3 increments
3.17 24
-2
Minus 2 increments
-1
Minus 1 increment
0
No adjustment
*
+1
Plus 1 increment
+2
Plus 2 increments
+3
Plus 3 increments
S E T S Y S T E M
(System Setting)
DATE/TIME
Date/Time
Set date and time for
UPS.
DATE YY/MM/DD
TIME HH:MM:SS
Date YY/MM/DD
Time HH/MM/SS
3.18 25
ChA Total Unit#
Number of
units in ChA
system parallel
connection
Set the number of
UPS units connected
in the UPS system.
1
*3
1 unit
*2
3.19 26
2
2 units
3
3 units
4
4 units
5
5 units
6
6 units
7
7 units
8
8 units
ChB Total Unit#
Number of
units in ChB
system parallel
connection
Do not change this
setting .
1
Do not change this
setting.
*
3.19 26
2
3
4
5
6
7
8
Redundancy
UPS operation
system
Redundant operation,
or single / parallel
operation
N+1
Redundant operation
3.20 27
None
Single /
parallel operation
*
INPUT Phases
Input phase
★
Set number of input
phases of UPS
Single
Single phase, 2 wires
*
3.21 28
3Ph/4W *1
3 phases, 4 wires
S E T D E F A U L T
(Initialization)
S E T D E F A U L T
Reset to factory defaults
-
-
-
3.22 29
Do not set values marked with “*1”.
The default value of “*2” is different depending on the UPS model. If you reset the value using “
SET DEFAULT
”,
the value will not be set to its default but the one indicated by “*3”.
For settings marked with “
★
”, after you change their values, the values will not take effect until you restart
the UPS. Therefore, after changing the values, read §3.23 “Restarting UPS” and then start the UPS again.
For details on UPS operation, refer to the
A11J Instruction Manual. Before stopping the UPS, always be sure
to stop the load device first.
Note