39
3. SETTING
Home
menu
Settings group
Settings
Values
Default
setting
Display
Content
Description
Display
Description
S E T T I N G
(various
settings)
S E T I N / O U T
(input/output
setting)
Voltage
Output voltage
★
Set UPS output voltage.
Same as input voltage
200V
Output voltage 200V
*
220V
Output voltage 220V
230V
Output voltage 230V
240V
Output voltage 240V
208V
Output voltage 208V
FREQ Range
Synchronous
frequency
tracking range
★
Set range (%) at which the
output frequency tracks
input frequency
1%
±
1
%
3%
±
3
%
*
5%
±
5
%
Frequency
Output
frequency
★
Set output frequency.
Auto
Automatic selection
*
50Hz
Fixed at 50Hz
60Hz
Fixed at 60Hz
Display
Voltage current
display
Set input/output voltage and
current for measurements
display etc.
200V/200V(S)
200V/200V(S)
Differs
depending
on UPS
model
200V/100V
200V/100V
100V/200V
100V/200V
100V/100V
100V/100V
200V/200V
200V/200V
S E T I / F
(interface setting)
Interface
Interface
Set interface for using PC
interface connector.
Standalone
Standalone
WS
Workstation
*
Terminal
*1 Terminal
Baud Rate
Baud rate
Set baud rate for connection
with PC, LAN card, or
Workstation.
9600
9600bps
*
4800
4800bps
2400
2400bps
S E T O P E R A T I O N
(operation setting)
Start Condition
Specify operation
during power
recovery.
Set UPS operation to perform
when utility power recovers,
after UPS stops due to end of
battery discharge in power
outage.
Auto
Automatic
*
Any Condition
Always start
STOP
Stop
BATT>30%
Start when charging rate reaches 30%.
BATT>50%
Start when charging rate reaches 50%.
BATT>80%
Start when charging rate reaches 80%.
BUZZER
Buzzer sound
Set when the buzzer should
beep.
ALL
All
*
Group #1
Group 1
Group #2
Group 2
SILENT
Stop
OFF Operation
Operation of
OFF
Set how to turn off
on
the operation panel of the
main unit to stop the UPS.
1 Sec.
Turn off when pressed for 1 second.
*
3 Sec.
Turn off when pressed for 3 seconds.
Unique
Turn off by special operation.
OVER Load
Overload
operation
Set what to do after power
supply switches to bypass due
to overload.
Auto Ret BYP
Automatic recovery from bypass
Stay on BYP
Bypass power supply during overload
*
Output OFF
*1 Stop output
Output @OFF
Power supply
during OFF
★
Set output's power supply
state when UPS stops.
OFF
Stop output
*
BYPASS
Bypass power supply
S E T B A T T E R Y
(battery setting)
BATLV Timing
BATLV timing
Set when to issue battery
voltage low warning.
Voltage
When battery voltage threshold is detected
*
2 Min.
When 2 minutes left in battery capacity
3 Min.
When 3 minutes left in battery capacity
5 Min.
When 5 minutes left in battery capacity
10 Min.
When 10 minutes left in battery capacity
BATT TST Length
Battery test time Set duration to perform
battery test.
2 Min
Run for 2 minutes
*
5 Min.,
Run for 5 minutes
10 Min.
Run for 10 minutes
20 Min.
Run for 20 minutes
BATT TST Period
Battery test
schedule
Set when (number of days) to
run battery test
automatically.
180 days
Automatically every 180 days
*
90 days
Automatically every 90 days
30 days
Automatically every 30 days
None
No automatic testing
S E T F U N C T I O N
(function setting)
RUN TIM @PF
Operating period
during outage
Set the time from when UPS
starts backup to when it
stops output.
BATT END
Until end of battery discharge
*
10 Sec.
Stop output after 10 seconds
30 Sec.
Stop output after 30 seconds
1 Min.
Stop output after 1 minute
3 Min.
Stop output after 3 minutes
5 Min.
Stop output after 5 minutes
10 Min.
Stop output after 10 minutes
RING Output
Ring operation
Set whether to output RING
signal during UPS startup.
Output
Output
None
Do not output
*
Out Vol Adj.
Output voltage
adjustment
Set adjustment for rated
voltage set in 3.1.
Each increment of
adjustment is about 1V
-3
Minus 3 increments
-2
Minus 2 increments
-1
Minus 1 increment
0
No adjustment
*
+1
Plus 1 increment
+2
Plus 2 increments
+3
Plus 3 increments
S E T S Y S T E M
(system setting)
DATE/TIME
Date/Time
Set date and time for UPS.
DATE YY/MM/DD
TIME HH:MM:SS
Date YY/MM/DD
Time HH/MM/SS
ChA Total Unit#
Number of units
in ChA system
parallel
connection
Set the number of UPS units
connected in the UPS system.
1
1 unit
Differs
depending
on UPS
model
2
2 units connected
3
3 units connected
4
4 units connected
5
5 units connected
6
6 units connected
7
7 units connected
8
8 units connected
ChB Total Unit#
Number of units
in ChB system
parallel
connection
Do not change anything here.
1
Do not change anything here.
*
2
3
4
5
6
7
8
Redundancy
UPS operation
system
Redundant operation, or single
machine/parallel operation
N+1
Redundant operation
None
Single machine/parallel operation
*
INPUT Phases
Input phase
★
Specify input phase of UPS
Single
Single phase, 2 wires
*
3Ph/4W
*1 3 phases, 4 wires
S E T D E F A U L T
(initialization)
SET DEFAULT
Reset to factory default setting
-
-
-
★
: Settings that require restarting UPS *1: Do not set values to these settings.