3. SETTING 

Home 

menu

 

Settings group

 

Settings

Values

Default 

setting

Display

Content

Description

Display

Description

S E T T I N G  

(various 

settings)

 

S E T   I N / O U T  

(input/output 
setting) 

Voltage 

Output voltage 

 

Set UPS output voltage.   
Same as input voltage 

200V 

Output voltage 200V

 

220V 

Output voltage 220V

 

230V 

Output voltage 230V

 

240V 

Output voltage 240V

 

208V 

Output voltage 208V

 

FREQ Range 

Synchronous 

frequency 

tracking range

Set range (%) at which the 

output frequency tracks 

input frequency   

1% 

±

1

 

 

3% 

±

3

 

 

5% 

±

5

 

 

Frequency 

Output 
frequency  

 

Set output frequency.   

Auto 

Automatic selection

 

50Hz 

Fixed at 50Hz

 

60Hz 

Fixed at 60Hz

 

Display 

Voltage current 
display 

Set input/output voltage and 
current for measurements 
display  etc.  

200V/200V(S)

200V/200V(S)

Differs 

depending 

on UPS 

model 

200V/100V 

200V/100V 

100V/200V 

100V/200V 

100V/100V 

100V/100V 

200V/200V 

200V/200V 

S E T   I / F  

(interface setting) 

Interface 

Interface 

Set interface for using PC 
interface connector.   

Standalone 

Standalone 

 

WS 

Workstation 

* 

Terminal  

*1 Terminal 

 

Baud Rate 

Baud rate 

Set baud rate for connection 
with PC, LAN card, or 

Workstation.  

9600 

9600bps 

* 

4800 

4800bps 

 

2400 

2400bps 

 

S E T   O P E R A T I O N

(operation setting)

Start Condition

Specify operation 
during power 
recovery.  

Set UPS operation to perform 
when utility power recovers, 
after UPS stops due to end of 
battery discharge in power 
outage.  

Auto 

Automatic 

* 

Any Condition

Always start 

 

STOP 

Stop 

 

BATT>30% 

Start when charging rate reaches 30%.

 

BATT>50% 

Start when charging rate reaches 50%. 

 

BATT>80% 

Start when charging rate reaches 80%. 

 

BUZZER 

Buzzer sound 

Set when the buzzer should 
beep.  

ALL  

All

* 

Group #1 

Group 1 

 

Group #2 

Group 2 

 

SILENT 

Stop 

 

OFF Operation

Operation of 
OFF 

Set how to turn off 

 on 

the operation panel of the 
main unit to stop the UPS. 

1 Sec. 

Turn off when pressed for 1 second. 

* 

3 Sec. 

Turn off when pressed for 3 seconds. 

 

Unique 

Turn off by special operation.   

 

OVER Load 

Overload 
operation 

Set what to do after power 
supply switches to bypass due 
to overload.   

Auto Ret BYP

Automatic recovery from bypass

 

Stay on BYP

Bypass power supply during overload

* 

Output OFF 

*1 Stop output 

 

Output @OFF 

Power supply 
during OFF 

 

Set output's power supply 
state when UPS stops.   

OFF 

Stop output 

* 

BYPASS 

Bypass power supply 

 

S E T   B A T T E R Y  

(battery setting) 

BATLV Timing

BATLV timing 

Set when to issue battery 
voltage low warning.   

Voltage 

When battery voltage threshold is detected

* 

2 Min. 

When 2 minutes left in battery capacity

 

3 Min. 

When 3 minutes left in battery capacity

 

5 Min. 

When 5 minutes left in battery capacity

 

10 Min. 

When 10 minutes left in battery capacity

 

BATT TST Length

Battery test time Set duration to perform 

battery test.   

2 Min 

Run for 2 minutes

* 

5 Min., 

Run for 5 minutes

 

10 Min. 

Run for 10 minutes

 

20 Min. 

Run for 20 minutes

 

BATT TST Period

Battery test 
schedule 

Set when (number of days) to 
run battery test 
automatically.  

180 days 

Automatically every 180 days

* 

90 days 

Automatically every 90 days

 

30 days 

Automatically every 30 days

 

None 

No automatic testing

 

S E T   F U N C T I O N  

(function setting) 
 

RUN TIM @PF 

Operating period 
during outage 

Set the time from when UPS 
starts backup to when it 
stops output.   

BATT END 

Until end of battery discharge

* 

10 Sec. 

Stop output after 10 seconds

 

30 Sec. 

Stop output after 30 seconds

 

1 Min. 

Stop output after 1 minute

 

3 Min. 

Stop output after 3 minutes

 

5 Min. 

Stop output after 5 minutes

 

10 Min. 

Stop output after 10 minutes

 

RING Output 

Ring operation 

Set whether to output RING 
signal during UPS startup. 

Output 

Output 

 

None 

Do not output

* 

Out Vol Adj.

Output voltage 
adjustment 

Set adjustment for rated 
voltage set in 3.1.   
Each increment of 
adjustment is about 1V 

-3 

Minus 3 increments

 

-2 

Minus 2 increments

 

-1 

Minus 1 increment

 

 0 

No adjustment

* 

+1 

Plus 1 increment

 

+2 

Plus 2 increments

 

+3 

Plus 3 increments

 

S E T   S Y S T E M

 

(system setting) 

DATE/TIME 

Date/Time 

Set date and time for UPS. 

DATE YY/MM/DD
TIME HH:MM:SS

Date YY/MM/DD 

Time HH/MM/SS 

 

ChA Total Unit#

Number of units 
in ChA system 

parallel 
connection 

Set the number of UPS units 
connected in the UPS system. 

 

1 unit 

Differs 

depending 

on UPS 

model 

2 units connected

3 units connected

4 units connected

5 units connected

6 units connected

7 units connected

8 units connected

ChB Total Unit#

Number of units 
in ChB system 
parallel 
connection 

Do not change anything here. 

1

Do not change anything here.   

* 

2

 

3

 

4

 

5

 

6

 

7

 

8

 

Redundancy 

UPS operation 
system 

Redundant operation, or single 
machine/parallel operation 

N+1 

Redundant operation

 

None 

Single machine/parallel operation 

* 

INPUT Phases

Input phase   

Specify input phase of UPS

Single 

Single phase, 2 wires

* 

3Ph/4W     

*1 3 phases, 4 wires

 

S E T   D E F A U L T

(initialization) 

SET DEFAULT 

Reset to factory default setting 

- 

- 

- 

: Settings that require restarting UPS    *1: Do not set values to these settings. 

Summary of Contents for A11J

Page 1: ...LCD Panel Operating Manual M0009235E...

Page 2: ...ing Frequency 10 3 4 Setting Voltage for Measurement Display 11 3 5 Setting PC Interface 12 3 6 Setting Baud Rate 13 3 7 Setting UPS Operation Upon Power Recovery 14 3 8 Setting Buzzer Condition 15 3...

Page 3: ...rning LED WARNING Red Lights Caution warning malfunction or end of battery discharge Output LED OUTPUT Green Lights When supplying power by inverter operation Blinks When supplying power by bypass ope...

Page 4: ...s 8 to 29 Setting setting Change various UPS settings Settings Input output voltage frequency display Interface interface baud rate Operation startup condition buzzer sound off operation overload oper...

Page 5: ...een may be different from the text and position described in the operating manual STATUS Note S E T T IN G S E T OP E R AT I O N Press to return to previous level Press to move to next level S E T T I...

Page 6: ...ous malfunction Output Stop HV Bypass output stopped excessive voltage FIN Temp Error Fin temperature error serious malfunction Over Load Overload DSP Error Controller error serious malfunction Vo V F...

Page 7: ...NT OUTPUT MEASUREMENT BATTERY MEASUREMENT CHARGER MEASUREMENT TEMPERATURE MEASUREMENT Vin V Iout A LF Watt kW Fout Hz ChgRate RunTm Min Ichg A MEASUREMENT T Amb C POWER Failure Times BATTERY Life Year...

Page 8: ...er recovery operation Set UPS operation to perform when utility power recovers after UPS stops due to end of battery discharge in power outage Auto Auto start 3 7 14 Any Condition Always start STOP St...

Page 9: ...5 ChA Total Unit Number of units in ChA system parallel connection Set the number of UPS units connected in the UPS system 1 3 1 unit 2 3 19 26 2 2 units 3 3 units 4 4 units 5 5 units 6 6 units 7 7 un...

Page 10: ...e Settings group Settings Home menu STATUS MEASUREMENT SETTING MAINTENANCE CONTROL SETTING SET IN OUT SET IN OUT Voltage SET I F SET OPERATION SET BATTERY SET FUNCTION SET SYSTEM FREQ Range Frequency...

Page 11: ...he UPS tends to switch to the asynchronous operation To connect to output of the engine power generator select 5 During the asynchronous operation if the UPS switches to the bypass operation this will...

Page 12: ...lues screen the value shown is the current value which is indicated by 4 When a value has been changed and accepted it is indicated by After you restart the UPS the indication becomes current value Ti...

Page 13: ...sp la y 200V 200V S Values 100V 100V Display 200V 100V 1 2 3 Details on settings and values Value Description 200V 200V S If rated input voltage and output voltage are both 200V type This is the defa...

Page 14: ...ATION SET BATTERY SET FUNCTION SET SYSTEM Baud Rate In te rf ac e WS Values Terminal Interface Standalone 1 2 3 Details on settings and values Value Description Standalone Standalone Select this value...

Page 15: ...NTROL SETTING SET I F SET I F Baud Rate SET OPERATION SET BATTERY SET FUNCTION SET SYSTEM Ba ud R at e 9600 Values 2400 Baud Rate 4800 1 2 3 Details on settings and values Value Description 9600 Baud...

Page 16: ...ass power is used BATT 30 More than 30 The UPS restarts automatically when battery charge reaches 30 if the utility power recovers BATT 50 More than 50 The UPS restarts automatically when battery char...

Page 17: ...tery operation battery testing battery voltage error low battery voltage overload bypass operation battery life end warning battery life end serious malfunction minor malfunction end of discharge requ...

Page 18: ...L SET I F SET BATTERY SET FUNCTION SET SYSTEM OFF Operation 1 Sec Values Unique SELECT OK BACK Cancel Example Shut down UPS in 3 Sec 3 seconds Confirm Accept SE TT IN G SET IN OUT SETTING SET OPERATIO...

Page 19: ...eep on pressing until you see it again 2 To return to the previous level press 3 When you switch to the values screen the value shown is the current value which is indicated by 4 When a value has been...

Page 20: ...ription OFF Stop When the button is OFF the UPS stops and power is not supplied BYPASS Bypass power supply When the button is OFF power switches to bypass power supply continues Default SET OPERATION...

Page 21: ...the battery s remaining capacity is less than 5 minutes issue warning 10 Min 10 minutes When the battery s remaining capacity is less than 10 minutes issue warning The time minutes is only an approxim...

Page 22: ...Details on settings and values Value Description 2 Min 2 minutes Run battery test for 2 minutes 5 Min 5 minutes Run battery test for 5 minutes 10 Min 10 minutes Run battery test for 10 minutes 20 Min...

Page 23: ...ery 90 days 30 Days 30 days Run battery test automatically every 30 days None No Do not run battery test automatically This function is available only when Auto is set in 3 3 Setting Frequency If 50Hz...

Page 24: ...minute Provide backup for 1 minute and then stop output supply 3 Min 3 minutes Provide backup for 3 minutes and then stop output supply 5 Min 5 minutes Provide backup for 5 minutes and then stop outp...

Page 25: ...T I F SET SYSTEM RING Output None Values 1 2 3 Details on settings and values Value Description None Do not output RING signal Output Output RING signal when the UPS starts If Output is selected it is...

Page 26: ...l on the plus side about 1V 2 Set 2 levels on the plus side about 2V 3 Set 3 levels on the plus side about 3V Adjustment can be made by specifying the number of levels with each level being about 1V T...

Page 27: ...the previous level press 3 When you switch to the values screen the value shown is the current value which is indicated by 4 When a value has been changed and accepted it is indicated by current value...

Page 28: ...Unit 1 Values 2 1 2 3 Details on settings and values Value Description 1 One UPS unit is used The default is different depending on the UPS model 2 2 UPS units are connected 3 3 UPS units are connect...

Page 29: ...operation system where there is one UPS unit Parallel operation system where total capacity of UPS units in parallel connection is used as connectable load capacity in operation If N 1 is selected wh...

Page 30: ...se this value SELECT OK BACK Cancel Default STATUS Example Set input phase to 3Ph 4W 3 phases 4 wires Confirm Accept SE TT IN G SET IN OUT INPUT Phases 3Ph 4W SET OPERATION SET BATTERY SET FUNCTION SE...

Page 31: ...TUS Example Resetting the settings Confirm SE TT IN G SET IN OUT SET OPERATION SET BATTERY SET FUNCTION SETTING SET DEFAULT SET SYSTEM SETTING SET DEFAULT Reset For the following settings resetting th...

Page 32: ...then start it is different For details refer to UPS Operation in the A11J Instruction Manual Before you stop the UPS be sure to stop the load devices first What is restarting Stop load devices Stop U...

Page 33: ...K Normal termination STATUS Test status Test Condition Test result Possible Test can start 4 2 34 Impossible Test cannot start Testing Test in progress Last Test Time Date of last test YY MM DD HH MM...

Page 34: ...scription Test Condition Test condition Possible Test can start Impossible Test cannot start Testing Test in progress Last Test Time Date and time of last battery test YY MM DD HH MM YY MM DD HH MM If...

Page 35: ...MAIN MCCB is set to OFF UPS s OFF operation is performed Battery test is canceled by power management software Note on battery test Cases where battery test is not possible While inverter stops During...

Page 36: ...Condition Last Test Time YY MM DD HH MM Last Result BA TT ER Y TE ST St ar t Battery test s displayed content Item Content Display Description Display Description Test Condition Test condition Possib...

Page 37: ...until you see it again 2 To return to the previous level press 3 If Wait appears use to go back and try again If the operation still fails contact your supplier or SANYO DENKI SETTING BYPASS CONTROL...

Page 38: ...peration with instant interruption You can also switch the UPS operation to the bypass operation using Forced Bypass inside the front panel of the UPS Note that during the bypass operation if you set...

Page 39: ...rvice technician to perform maintenance of the UPS Even though details are described in 6 Menu List do not use the menu to perform any operation This term is used to indicate service technicians from...

Page 40: ...or malfunction LF CHG Load factor Charging rate Total Unit Err Total number of units error serious malfunction LF Tim m Load factor Charging duration minutes LCD Error LCD panel error Byp Fuse Error B...

Page 41: ...iming Set when to issue battery voltage low warning Voltage When battery voltage threshold is detected 2 Min When 2 minutes left in battery capacity 3 Min When 3 minutes left in battery capacity 5 Min...

Page 42: ...erent depending on UPS model 10Min 10 minutes 15Min 15 minutes 25Min 25 minutes 30Min 30 minutes 35Min 35 minutes 45Min 45 minutes 60Min 60 minutes 120Min 120 minutes 180Min 180 minutes 360Min 360 min...

Page 43: ...number of load devices Bypass SW ON Bypass switch ON The forced bypass switch Forced Bypass is set to Bypass Req To Restart Restart is necessary Values for settings are changed but they require resta...

Page 44: ...s However the operating time of which the battery charging rate will be correctly indicated differs depending on the specifications of the UPS configuration of the battery 4 The value indicated by Chg...

Reviews: