The following table lists details about UPS states that appear on the LCD screen in the 

“STATUS”

 home menu. If you cannot 

resolve the problem when the UPS malfunctions, contact your supplier or SANYO DENKI.   

 

UPS mode 

State display 

Display 

Description Display 

Description 

Details and solution 

STANDBY 

 

ONLINE 

 

BYPASS 

 

 

BATTERY 

 
 

BATT TEST 

 
 

SYS FAILURE

 

 

Standby 
 

Online 

 

During bypass 

operation 

 

During battery 
operation 

 

During battery 

testing 

 

During system 

malfunction 
 

Output Not Sync

Asynchronous operation 

Power supply is asynchronous with input power source.   

Switching to bypass operation is instant cutoff switching.   

Input Freq Err 

Input frequency error 

The input power source exceeds the acceptable frequency range. If it 

occurs during normal operation, power supply automatically switches 

to battery. If this problem occurs frequently, check the input power 

source and the UPS frequency setting.   

Input Vol Hi 

High input voltage 

The input power source exceeds the acceptable voltage range. If it 

occurs during normal operation, power supply automatically switches 

to battery. If this problem occurs frequently, check the input power 

source and the UPS frequency setting.   

Input Vol Low 

Low input voltage 

Input Error 

Input error 

Instant disconnection of input power source is detected. If it occurs 

during normal operation, power supply automatically switches to 

battery. If this problem occurs frequently, check the input power source 

and the UPS frequency setting.   

INV Vol Hi 

High inverter voltage 
(serious malfunction) 

Inverter output voltage error is detected.   

UPS is malfunctioning. Contact your supplier or SANYO DENKI.   

INV Vol Low 

Low inverter voltage   
(serious malfunction) 

INV Vol Error 

Inverter voltage detection 
circuit error 

(serious malfunction)

UPS is malfunctioning. Contact your supplier or SANYO DENKI. 

Output Stop (HV)

Bypass output stopped 

(excessive voltage) 

Power supply stops because input over voltage is detected during 

bypass operation.   

OverLoad 

Overload 

There are a lot of load devices connected to the UPS to exceed the UPS 

rated capacity. Reduce the number of load devices. 

Vo=   V Fo=   Hz

Output voltage, output 

frequency

Output voltage, output frequency 

Vi=   V Fi=   Hz

Input voltage, input 

frequency

Input voltage, input frequency 

LF=   % CHG=  % 

*

Load factor    %, Charging 

rate  %

Load factor    %, Charging rate    % 

LF=   % Tim=  m 

*

Load factor    %, Charging 

duration  minutes 

Load factor    %, Charging duration    minutes 

Byp Fuse Error 

Bypass fuse error 

There are a lot of load devices connected to the UPS to exceed the UPS 

rated capacity. As a result, the 

 MAIN MCCB  

trips. 

Reduce the number of load devices. 

Bypass SW ON 

Bypass switch ON 

The forced bypass switch   

Forced Bypass

    is set to “Bypass”. 

Req To Restart 

Restart is necessary.   

Values for settings are changed but they require restart of the UPS 

before their changes take effect. Therefore, see §3.23 “Restarting UPS” 

and then restart the UPS. 

Remote 

Battery test by remote 

operation in progress 

Battery test is in progress by remote operation of power management 

software.  

Remote OFF 

Operation stops due to 

remote OFF.   

Inverter startup operation is canceled because remote OFF signal is 

input.  

EPO ON 

Operation stopping due to 

EPO.  

Inverter startup operation is canceled because EPO signal is input.   

Batt Life End 

End of battery life 

The battery life has come to an end. Replace the battery.   

Batt Life Warn 

Battery life end warning 

The battery will last for 6 more months. Prepare to replace the battery. 

Batt Vol Error 

Battery voltage error 

No battery pack is connected. Make sure a battery pack is installed. 

Batt Vol End 

End of battery discharge 

Battery discharge has ended.   

Batt Vol Low 

Low battery voltage 

Battery voltage is low.   

CHG Error 

Charger error 

(serious malfunction) 

UPS is malfunctioning. Contact your supplier or SANYO DENKI.   

CONV Error 

Converter error

(serious malfunction) 

UPS is malfunctioning. Contact your supplier or SANYO DENKI.   

FIN Temp Error 

Fin temperature error

(serious malfunction) 

UPS is malfunctioning. Contact your supplier or SANYO DENKI. 

DSP Error 

Controller error 

(serious malfunction)

UPS is malfunctioning. Contact your supplier or SANYO DENKI. 

BUS Error 

DC voltage error 

(serious malfunction)

UPS is malfunctioning. Contact your supplier or SANYO DENKI. 

AUX2 Error 

Auxiliary power error

(minor malfunction)

UPS is malfunctioning. Contact your supplier or SANYO DENKI. 

BF Circuit Error

Back feed prevention circuit 

error (serious malfunction)

UPS is malfunctioning. Contact your supplier or SANYO DENKI. 

Total Unit# Err

Total number of units error 

(serious malfunction) 

The number of UPS units set in §3.19 is different from the actual 

number of UPS units operating. 

Check the setting and the actual number of UPS units.

LCD Error 

LCD panel error 

The LCD panel is malfunctioning. Contact your supplier or SANYO 

DENKI.  

Minor Error 

Minor malfunction 

Contact your supplier or SANYO DENKI. 

Fatal Error 

Serious malfunction 

UPS is malfunctioning. Contact your supplier or SANYO DENKI. 

FT Disabled 

Redundant operation not 

allowed 

In §3.20, if the operation system is set to “N+1”: there is a lot of load 

capacity connected to the UPS so that parallel redundant operation is 

not possible. Reduce the number of connected load devices. 

Check Unit Error

Device error exists and 

checking is required. 

There may be communication error between units. 
Check the cable connecting the units.   

 

* Refer to §8 “Notes on UPS Measurements Information.” 

Summary of Contents for A11J

Page 1: ...LCD Panel Operating Manual M0009235E...

Page 2: ...ing Frequency 10 3 4 Setting Voltage for Measurement Display 11 3 5 Setting PC Interface 12 3 6 Setting Baud Rate 13 3 7 Setting UPS Operation Upon Power Recovery 14 3 8 Setting Buzzer Condition 15 3...

Page 3: ...rning LED WARNING Red Lights Caution warning malfunction or end of battery discharge Output LED OUTPUT Green Lights When supplying power by inverter operation Blinks When supplying power by bypass ope...

Page 4: ...s 8 to 29 Setting setting Change various UPS settings Settings Input output voltage frequency display Interface interface baud rate Operation startup condition buzzer sound off operation overload oper...

Page 5: ...een may be different from the text and position described in the operating manual STATUS Note S E T T IN G S E T OP E R AT I O N Press to return to previous level Press to move to next level S E T T I...

Page 6: ...ous malfunction Output Stop HV Bypass output stopped excessive voltage FIN Temp Error Fin temperature error serious malfunction Over Load Overload DSP Error Controller error serious malfunction Vo V F...

Page 7: ...NT OUTPUT MEASUREMENT BATTERY MEASUREMENT CHARGER MEASUREMENT TEMPERATURE MEASUREMENT Vin V Iout A LF Watt kW Fout Hz ChgRate RunTm Min Ichg A MEASUREMENT T Amb C POWER Failure Times BATTERY Life Year...

Page 8: ...er recovery operation Set UPS operation to perform when utility power recovers after UPS stops due to end of battery discharge in power outage Auto Auto start 3 7 14 Any Condition Always start STOP St...

Page 9: ...5 ChA Total Unit Number of units in ChA system parallel connection Set the number of UPS units connected in the UPS system 1 3 1 unit 2 3 19 26 2 2 units 3 3 units 4 4 units 5 5 units 6 6 units 7 7 un...

Page 10: ...e Settings group Settings Home menu STATUS MEASUREMENT SETTING MAINTENANCE CONTROL SETTING SET IN OUT SET IN OUT Voltage SET I F SET OPERATION SET BATTERY SET FUNCTION SET SYSTEM FREQ Range Frequency...

Page 11: ...he UPS tends to switch to the asynchronous operation To connect to output of the engine power generator select 5 During the asynchronous operation if the UPS switches to the bypass operation this will...

Page 12: ...lues screen the value shown is the current value which is indicated by 4 When a value has been changed and accepted it is indicated by After you restart the UPS the indication becomes current value Ti...

Page 13: ...sp la y 200V 200V S Values 100V 100V Display 200V 100V 1 2 3 Details on settings and values Value Description 200V 200V S If rated input voltage and output voltage are both 200V type This is the defa...

Page 14: ...ATION SET BATTERY SET FUNCTION SET SYSTEM Baud Rate In te rf ac e WS Values Terminal Interface Standalone 1 2 3 Details on settings and values Value Description Standalone Standalone Select this value...

Page 15: ...NTROL SETTING SET I F SET I F Baud Rate SET OPERATION SET BATTERY SET FUNCTION SET SYSTEM Ba ud R at e 9600 Values 2400 Baud Rate 4800 1 2 3 Details on settings and values Value Description 9600 Baud...

Page 16: ...ass power is used BATT 30 More than 30 The UPS restarts automatically when battery charge reaches 30 if the utility power recovers BATT 50 More than 50 The UPS restarts automatically when battery char...

Page 17: ...tery operation battery testing battery voltage error low battery voltage overload bypass operation battery life end warning battery life end serious malfunction minor malfunction end of discharge requ...

Page 18: ...L SET I F SET BATTERY SET FUNCTION SET SYSTEM OFF Operation 1 Sec Values Unique SELECT OK BACK Cancel Example Shut down UPS in 3 Sec 3 seconds Confirm Accept SE TT IN G SET IN OUT SETTING SET OPERATIO...

Page 19: ...eep on pressing until you see it again 2 To return to the previous level press 3 When you switch to the values screen the value shown is the current value which is indicated by 4 When a value has been...

Page 20: ...ription OFF Stop When the button is OFF the UPS stops and power is not supplied BYPASS Bypass power supply When the button is OFF power switches to bypass power supply continues Default SET OPERATION...

Page 21: ...the battery s remaining capacity is less than 5 minutes issue warning 10 Min 10 minutes When the battery s remaining capacity is less than 10 minutes issue warning The time minutes is only an approxim...

Page 22: ...Details on settings and values Value Description 2 Min 2 minutes Run battery test for 2 minutes 5 Min 5 minutes Run battery test for 5 minutes 10 Min 10 minutes Run battery test for 10 minutes 20 Min...

Page 23: ...ery 90 days 30 Days 30 days Run battery test automatically every 30 days None No Do not run battery test automatically This function is available only when Auto is set in 3 3 Setting Frequency If 50Hz...

Page 24: ...minute Provide backup for 1 minute and then stop output supply 3 Min 3 minutes Provide backup for 3 minutes and then stop output supply 5 Min 5 minutes Provide backup for 5 minutes and then stop outp...

Page 25: ...T I F SET SYSTEM RING Output None Values 1 2 3 Details on settings and values Value Description None Do not output RING signal Output Output RING signal when the UPS starts If Output is selected it is...

Page 26: ...l on the plus side about 1V 2 Set 2 levels on the plus side about 2V 3 Set 3 levels on the plus side about 3V Adjustment can be made by specifying the number of levels with each level being about 1V T...

Page 27: ...the previous level press 3 When you switch to the values screen the value shown is the current value which is indicated by 4 When a value has been changed and accepted it is indicated by current value...

Page 28: ...Unit 1 Values 2 1 2 3 Details on settings and values Value Description 1 One UPS unit is used The default is different depending on the UPS model 2 2 UPS units are connected 3 3 UPS units are connect...

Page 29: ...operation system where there is one UPS unit Parallel operation system where total capacity of UPS units in parallel connection is used as connectable load capacity in operation If N 1 is selected wh...

Page 30: ...se this value SELECT OK BACK Cancel Default STATUS Example Set input phase to 3Ph 4W 3 phases 4 wires Confirm Accept SE TT IN G SET IN OUT INPUT Phases 3Ph 4W SET OPERATION SET BATTERY SET FUNCTION SE...

Page 31: ...TUS Example Resetting the settings Confirm SE TT IN G SET IN OUT SET OPERATION SET BATTERY SET FUNCTION SETTING SET DEFAULT SET SYSTEM SETTING SET DEFAULT Reset For the following settings resetting th...

Page 32: ...then start it is different For details refer to UPS Operation in the A11J Instruction Manual Before you stop the UPS be sure to stop the load devices first What is restarting Stop load devices Stop U...

Page 33: ...K Normal termination STATUS Test status Test Condition Test result Possible Test can start 4 2 34 Impossible Test cannot start Testing Test in progress Last Test Time Date of last test YY MM DD HH MM...

Page 34: ...scription Test Condition Test condition Possible Test can start Impossible Test cannot start Testing Test in progress Last Test Time Date and time of last battery test YY MM DD HH MM YY MM DD HH MM If...

Page 35: ...MAIN MCCB is set to OFF UPS s OFF operation is performed Battery test is canceled by power management software Note on battery test Cases where battery test is not possible While inverter stops During...

Page 36: ...Condition Last Test Time YY MM DD HH MM Last Result BA TT ER Y TE ST St ar t Battery test s displayed content Item Content Display Description Display Description Test Condition Test condition Possib...

Page 37: ...until you see it again 2 To return to the previous level press 3 If Wait appears use to go back and try again If the operation still fails contact your supplier or SANYO DENKI SETTING BYPASS CONTROL...

Page 38: ...peration with instant interruption You can also switch the UPS operation to the bypass operation using Forced Bypass inside the front panel of the UPS Note that during the bypass operation if you set...

Page 39: ...rvice technician to perform maintenance of the UPS Even though details are described in 6 Menu List do not use the menu to perform any operation This term is used to indicate service technicians from...

Page 40: ...or malfunction LF CHG Load factor Charging rate Total Unit Err Total number of units error serious malfunction LF Tim m Load factor Charging duration minutes LCD Error LCD panel error Byp Fuse Error B...

Page 41: ...iming Set when to issue battery voltage low warning Voltage When battery voltage threshold is detected 2 Min When 2 minutes left in battery capacity 3 Min When 3 minutes left in battery capacity 5 Min...

Page 42: ...erent depending on UPS model 10Min 10 minutes 15Min 15 minutes 25Min 25 minutes 30Min 30 minutes 35Min 35 minutes 45Min 45 minutes 60Min 60 minutes 120Min 120 minutes 180Min 180 minutes 360Min 360 min...

Page 43: ...number of load devices Bypass SW ON Bypass switch ON The forced bypass switch Forced Bypass is set to Bypass Req To Restart Restart is necessary Values for settings are changed but they require resta...