27
§
3
3
.
.
2
2
0
0
S
S
e
e
t
t
t
t
i
i
n
n
g
g
O
O
p
p
e
e
r
r
a
a
t
t
i
i
o
o
n
n
S
S
y
y
s
s
t
t
e
e
m
m
This section describes how to specify the UPS operation system. You can choose between parallel redundant
operation or single machine/parallel operation.
①
Press
to display the LCD screen.
②
Press
to change the home menu to the one shown below.
③
Press
to accept it.
④
In the same way, follow the figure below to make selection at each level, as follows:
“Home menu”
→
“Setting group”
→
“Setting”
→
“Value”
⑤
Use
to switch values, and then press
to select a desired value. When the confirmation screen appears, press
again to accept the value.
⑥
Press
to return to the home menu.
Settings group
Settings
Home menu
STATUS
MEASUREMENT
SETTING
MAINTENANCE
CONTROL
SET I/F
Redundancy
>> None
Values
1
2
3
Details on settings and values
Value
Description
N+1
Parallel redundant
operation
* Parallel redundant operation system: where there is surplus
of one unit from UPS units in parallel connection to handle
load capacity
None
Single /
parallel operation
* Single operation system: where there is one UPS unit
* Parallel operation system: where total capacity of UPS units
in parallel connection is used as connectable load capacity in
operation
If “
N+1
” is selected, when there is no surplus of one UPS unit for load capacity connected to UPS,
the LCD screen displays “
FT Disabled
”. In this case, reduce the load connected to UPS.
However, the load factor value “
LF = %
” displayed by viewing UPS measurements is same even when
either setting value (“
N+1”
or
“
None
”) is set. See §8 “Notes on UPS Measurements Information” for
details.
[SELECT] = OK
[BACK] = Cancel
Default
STATUS
Example: Set operation system to “
N+1
”
Confirm
Accept
S E T T I N G
SET IN/OUT
Redundancy
N+1
SET OPERATION
SET BATTERY
SET FUNCTION
SETTING
SET SYSTEM
SET SYSTEM
Redundancy
INPUT Phases
SET SYSTEM
DATE/TIME
ChA Total Unit#
ChB Total Unit#
Redundancy
>> N+1
SET DEFAULT
*1. Pressing
repeatedly cycles through the
displayed items. If you miss a desired item,
just keep on pressing until you see it again.
*2. To return to the previous level, press
.
*3. When you switch to the values screen, the
value shown is the current value, which is
indicated by “
> >
” .
*4. When a value has been changed and accepted,
it is indicated by “
>>
” (current value).