manualshive.com logo in svg
background image

JOVYATLAS POWERMASTER S 6000-P       BAX 4469 E         

- 1 -                                            

 

 

 

Operating Manual 

 

UPS - System 

POWERMASTER S 6000-P

   

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

BAX 4469E 

Содержание JOVYATLAS POWERMASTER S 6000-P

Страница 1: ...JOVYATLAS POWERMASTER S 6000 P BAX 4469 E 1 Operating Manual UPS System POWERMASTER S 6000 P BAX 4469E...

Страница 2: ...R S 6000 P BAX 4469 E 2 Index Date Name Remarks 0 2012 04 23 Chr Fechteler Original 1 2014 06 13 Chr Fechteler 14 349 2 2014 11 06 Chr Fechteler 14 608 3 2015 07 22 Chr Fechteler 15 381 4 2015 09 25 C...

Страница 3: ...source of information W RTSIL JOVYATLAS EUROATLAS GmbH reserves the right to make any necessary changes to the contents and technology described in this operating manual without having to make an anno...

Страница 4: ...7 2 SHUTTING DOWN THE SINGLE UPS 15 7 3 COMMISSIONING THE UPS IN PARALLEL OPERATION 16 7 4 SHUTTING DOWN THE UPS IN PARALLEL OPERATION 16 8 OPERATION AND DISPLAYPANEL 17 8 1 PANEL 17 8 2 PARAMETER OF...

Страница 5: ...4 weeks after receipt in order to prevent the battery discharging itself 1 General Notes The device may only be opened by trained specialists The system is to be connected up and earthed according to...

Страница 6: ...tion During normal operation the battery and the inverter are supplied with power via a rectifier online operation The change over from alternating voltage to direct voltage and back to alternating vo...

Страница 7: ...pass operation In the case of a fault occurring in the inverter or an overload a switch over device switches the load back to the mains This means that in the case of a power failure the connected con...

Страница 8: ...ure 0 ms Overload switching Automatic overload switching by the UPS unit Noise level At an approx distance of 1 metre 55dB A Environment Temperature 0 C to 40 C 15 25 C recommended Air humidity 0 to 9...

Страница 9: ...BAX 4469 E 9 5 Views of JOVYATLAS Powermaster S 6000 P 5 1 Front and Rear View Figure 4 Front View Figure 5 Rear View and Terminal Block FAN COVER Panel Mounting Angles FAULT BYPASS ON BAT ON LINE ON...

Страница 10: ...RPACK S 6000 1 Figure 6 Front View POWERPACK S 6000 3 2 Figure 7 Rear View POWERPACK S 6000 4 Position Designation 1 Cover Plate left and right removable 2 Mounting and Retaining Bracket for 19 mounti...

Страница 11: ...outs 5 Connect the input cable to the terminals with the designation input L N PE 6 Connect the output cable to the terminals with the designation output L N PE 7 Fix the cover plate with a Phillips s...

Страница 12: ...cted in between the feeding mains and the UPS Figure 8 Using Reverse Voltage Protection If the reverse voltage protection is not used please connect the inputs like shown in picture below Figure 9 Wit...

Страница 13: ...Anlagen wird ein Kabel von USV 1 nach USV 2 sowie ein Kabel von USV 2 nach USV 3 geschaltet Es darf keine Ringverbindung geschaffen werden Figure 10 Connection of external Battery Packs 6 4 Connection...

Страница 14: ...JOVYATLAS POWERMASTER S 6000 P BAX 4469 E 14 Figure 11 Connection of a Parallel System UPS UPS UPS UPS Load MAINS...

Страница 15: ...ting down the single UPS 1 Push Button MENU ENTER to choose Menu UPS Command 2 Push Button MENU ENTER to choose Menu Start UPS ON OFF 3 Push Button MENU ENTER to choose Menu UPS runs to Bypass 4 Open...

Страница 16: ...Please check if all BYPASS LED s are not lighting all ON LINE LED are lighting the display will show message Line Mode Parallel Important Notice Prior to connecting the load to the output of the syste...

Страница 17: ...l flash in yellow when input voltage magnitude or frequency is out of tolerance ON LINE This LED will light up in green when the UPS is operating on line mode ON BAT This LED will light up in red when...

Страница 18: ...LD START LANGUAGE FAULT REC TIME CLEAR FAULT REC LCD VERSION CORE VERSION UPS SERIAL No DISABLE ENABLE Line config Disable 208 220 230 240V BATT TEST TIME BATT TEST PERIOD AUTO MANUAL TEST 1 2 3 DISAB...

Страница 19: ...S O P FREQ 50 0Hz Output Frequency of UPS BAT VOLT 276V Battery Voltage of Battery Pack O P LOAD 80 Load in Percent O P CURR 13A Load Current in Ampere O P W 2300W Load in Watt O P VA 3000VA Load in V...

Страница 20: ...al Failure check the PFC Rectifier Inverter fault Internal Failure check the Inverter Over temperature Check Function of the Fan or if something is blocking the Air Outlet Batt over volt Internal Fail...

Страница 21: ...llow data transmission between a computer and the UPS unit The UPS unit can be monitored and checked by a computer through the use of special software Switching off of the UPS unit in the case of powe...

Страница 22: ...tion of the external electronic STOP switch causes the output of the UPS unit to be switched to voltage free and the UPS unit shuts down In order to provide the consumers with a voltage again the elec...

Страница 23: ...e UPS unit to be switched voltage free and the UPS unit shuts down In order to supply consumers with voltage again it is necessary for the electronic STOP switch to be reset and for the UPS to be rest...

Страница 24: ...JOVYATLAS POWERMASTER S 6000 P BAX 4469 E 24 14 Circuit diagram relay board...

Страница 25: ...attery At the end of the bridging time the inverter switches off automatically and the consumers are no longer supplied with power When the mains power is restored the consumers begin again to be supp...

Страница 26: ...UPS has to be recharged in case of UPS is being switched off totally after latest four weeks It is sufficient to connect the UPS to an input mains The recharging time shall be at least 8 hours We reco...

Отзывы: