System Architecture
Connecting outdoor units and BACnet Gateway
- You can control up to 80 outdoor units and 256 indoor units using BACnet Gateway.
*Each communication channel of BACnet Gateway can be connected with 16 outdoor units.
- The more outdoor units are connected, the longer time takes for tracking.
OnOff
controller
Outdoor
Unit
RS 485
BACnet Gateway
Internet
BMS system
BMS Engineering
TRANE Engineering
Max 256 Indoor units
(DVM Series)
For the devices which support new communication, set the communication channel
mode on '[System setting]-[Tracking]' menu as 'NEW' and for SIM/PIM which conventional
communication is applied, set the communication channel mode as 'IM'. You cannot
connect indoor & outdoor unit SET which conventional communication is applied to new
communication BACnet Gateway.
When setting communication channel mode as 'NEW', the address of virtual centralized
control will be assigned.
Channel 0: Virtual OnOff controller 11, Channel 1: Virtual OnOff controller 12,
Channel 2: Virtual OnOff controller 13, Channel 4: Virtual OnOff controller 14,
Channel 5: Virtual OnOff controller 15