If communication error occurs on devices such as SIM/Centralized Controller/
Interface Module etc, other functions such as power distribution may also
create a problem. You must have BMS system to check the errors and you must
take action immediately.
Instance
Number
Control and
Monitoring
Object
Type
Object Name
Status Value
1
All device OFF
BO
ALL_OFF_xx
Inactive : All devices Off
2
DMS2 Status
AI
DMS2_Status_xx
0: Normal, 8: Emergency stop,
105 : Tracking in progress,
108 : Tracking failed
109 : DMS2
↔
BACnet
Communication failed
3
BACnet error
code
AI
BACnetApp_Error_
Code_xx
BACnet error code
4
Gateway
Notify
NC
GW_Notify_xx
When the error occurred, send event to list
of destination in the recipient_list.
(Max : 8)
BACnet Gateway has following point list.
BACnet Gateway
DDC has following point list.
Instance
Number
Object
Object
Type
Object Name
Unit
Status value
Inactive Active
Text-1 Text-2 Text-3 Text-4 Text-5
1
Digital Input 1
BI DI_01_xx_xx (BACnet Gateway Reserved)
Off
On
2
Digital Input 2
BI DI_02_xx_xx (BACnet Gateway Reserved)
Off
On
3
Digital Input 3
BI DI_03_xx_xx
Off
On
4
Digital Input 4
BI DI_04_xx_xx
Off
On
5
Digital Input 5
BI DI_05_xx_xx
Off
On
6
Digital Input 6
BI DI_06_xx_xx
Off
On
7
Digital Input 7
BI DI_07_xx_xx
Off
On
8
Digital Input 8
BI DI_08_xx_xx
Off
On
9
Digital Input 9
BI DI_09_xx_xx
Off
On
10
Digital Input 10
BI DI_10_xx_xx
Off
On
11
Digital Output 1 BO DO_01_xx_xx (BACnet Gateway Reserved)
Off
On
12
Digital Output 2 BO DO_02_xx_xx (BACnet Gateway Reserved)
Off
On
13
Digital Output 3 BO DO_03_xx_xx
Off
On
14
Digital Output 4 BO DO_04_xx_xx
Off
On
15
Digital Output 5 BO DO_05_xx_xx
Off
On
16
Digital Output 6 BO DO_06_xx_xx
Off
On
17
Digital Output 7 BO DO_07_xx_xx
Off
On
18
Digital Output 8 BO DO_08_xx_xx
Off
On
DDC
BACnet Point List (Continued)
NASAS_MIM-B17N_BACnet Gateway_IM_EN_03719A(1).indd 66
2013-04-25 오전 10:14:42