BACnet Point List (Continued)
EHS
Single EHS Unit has following point list.
Instance
Number
Object
Object
Type
Object Name
Unit
Status value
Inactive Active
Text-1 Text-2
Text-3
Text-4
1
Room temperature
AI
EHS_RoomTemp_xx_xxxxxx
°C
2
Set temperature
AV
EHS_Temp_Set_xx_xxxxxx
°C
Use when displayed temperature type
is set to 'Room'.
3
Set temperature of water out
AV
EHS_WaterOutTemp_Set_xx_xxxxxx
°C
Use when displayed temperature type
is set to 'WaterOut'.
4
Set temperature of hot water
AV
EHS_HotWaterTemp_Set_xx_xxxxxx
°C
5
Setting lower temperature limit
AV
EHS_Cool_LimitTemp_xx_xxxxxx
°C
Use when displayed temperature type
is set to 'Room'.
6
Setting upper temperature limit
AV
EHS_Heat_LimitTemp_xx_xxxxxx
°C
Use when displayed temperature type
is set to 'Room'.
7
Lower temperature limit for water out
AV
EHS_WOCoolLimitTemp_xx_xxxxxx
°C
8
Upper temperature limit for water out
AV
EHS_WOHeatLimitTemp_xx_xxxxxx
°C
9
Upper temperature limit for hot water
AV
EHS_WTHeatlLimitTemp_xx_xxxxxx
°C
10
The power value after the basic date
AI
EHS_Baseline_kWh_xx_xxxxxx
kWh
11
The number of hours usage of an
indoor unit after the basic date
AI
EHS_Baseline_Minute_xx_xxxxxx
Minute
12
Power value within period
AI
EHS_Period_kWh_xx_xxxxxx
kWh
13
The number of hours usage of an
indoor unit within period
AI
EHS_Period_Minute_xx_xxxxxx
Minute
14
Current temperature of water out
AI
EHS_WOCurrentTemp_xx_xxxxxx
°C
15
Current temperature of hot water
AI
EHS_HotWaterTemp_xx_xxxxxx
°C
16
Displayed temperature type
BI
EHS_ControlTempType_xx_xxxxxx
Room WaterOut
17
Thermostat usage
BI
EHS_Thermostat_xx_xxxxxx
False
True
18
Outing
BI
EHS_GoOut_xx_xxxxxx
Off
On
19
Power On/Off
BV
EHS_Power_xx_xxxxxx
Off
On
20
Setting lower temperature limit
BV
EHS_Cool_LimitTemp_Set_xx_xxxxxx
False
True Use when displayed tempera-
ture type is set to 'Room'.
21
Setting upper temperature limit
BV
EHS_Heat_LimitTemp_Set_xx_xxxxxx False
True Use when displayed tempera-
ture type is set to 'Room'.
22
Apply lower temperature limit for
water out
BV
EHS_WOCoolLimitFlag_xx_xxxxxx
False
True Use when displayed tempera-
ture type is set to 'WaterOut'.
23
Apply upper temperature limit for
water out
BV
EHS_WOHeatLimitFlag_xx_xxxxxx
False
True Use when displayed tempera-
ture type is set to 'WaterOut'.
24
Apply upper temperature limit for hot water BV
EHS_WTHeatLimitFlag_xx_xxxxxx
False
True
25
On/Off status of hot water mode
BV
EHS_HotWater_Power_xx_xxxxxx
Off
On
26
Status of quiet operation
BV
EHS_Sleep_xx_xxxxxx
Off
On
27
Operation mode status
MV EHS_Operation_Mode_xx_xxxxxx
Auto
Cool
Heat
28
Operation mode limit status
MV EHS_Mode_Limit_xx_xxxxxx
No Limit Cool
Only
Heat Only
29
Remote controller limit status
MV EHS_Remocon_Limit_xx_xxxxxx
Enable RC Disable
RC
Conditional
RC
30
Status of hot water operation mode
MV EHS_HotWater_Mode_xx_xxxxxx
Force
Eco
Standard
Power
31
Integrated error code of both indoor
unit and outdoor unit
AI
EHS_Error_Code_xx_xxxxxx
32
EHS notifiy
NC
EHS_Notify_xx_xxxxxx
When the error occurred, send event to list of
destination in the recipient_list. (Max : 8)