E-
22
Reading EHP Watt-hour Meter
Setting and checking watt-hour meter
1
Click [System and Checking Watt-hour meter].
You can change settings on watt-hour meter only when SIM/PIM interface
module is connected.
2
Click [Edit] from the 'Setting and checking Watt-hour meter' screen.
CT proportion is set to ‘1’ as factory default value.
3
Set the [Name] and [CT proportion] for the watt-hour meter.
You can use maximum 16 letters for name and only available special characters
are “.”, ”,”, ”_”, ”-“, and “space”.
Value for CT proportion should be integer between range of 1 ~ 5000.
4
Click [Save].
CT proportion value will be saved to the BACnet Gateway.
If you do not click [Save] changed setting will not be saved.
5
Watt-hour meter value will display the actual value of electricity on the
corresponding watt-hour meter. Value will be updated automatically.
When using CT watt-hour meter, be careful that there can be difference with
actual power consumption as much as CT ratio error.
1
3
2
4