Single indoor unit has following point list.
Instance
Number
Object
Object
Type
Object Name
Unit
Status value
Inactive Active
Text-1 Text-2
Text-3 Text-4 Text-5
1
Indoor Temperature
AI AC_RoomTemp_xx_xxxxxx
°C
2
Set temperature
AV AC_Temp_Set_xx_xxxxxx
°C
3
Setting lower temperature limit
AV AC_Cool_LimitTemp_xx_xxxxxx
°C
4
Setting upper temperature limit AV AC_Heat_LimitTemp_xx_xxxxxx
°C
5
The power value of an indoor
unit after the basic date
AI AC_Baseline_kWh_xx_xxxxxx
kWh
6
The number of hours usage of an
indoor unit after the basic date
AI AC_Baseline_Minute_xx_
xxxxxx
Minute
7
Power value within period
AI AC_Period_kWh_xx_xxxxxx
kWh
8
The number of hours usage of
an indoor unit within period
AI AC_Period_Minute_xx_xxxxxx Minute
9
Power On/Off
BV AC_Power_xx_xxxxxx
Off
On
10
Applying lower temperature
limit setting
BV AC_Cool_Limit_set_xx_xxxxxx
False
True
11
Applying upper temperature
limit setting
BV AC_Heat_Limit_set_xx_xxxxxx False
True
12
Filter sign status
BI AC_FilterSign_xx_xxxxxx
False
True
13
Filter sign reset
BO AC_FilterSign_Reset_xx_xxxxxx False
True
14
Operation mode status
MV AC_Operation_Mode_xx_
xxxxxx
Auto
Cool
Heat
Fan
Dry
15
Fan speed status
MV AC_FanSpeed_xx_xxxxxx
Auto
Low
Mid
High
16
Air flow direction status
MV AC_FanFlow_xx_xxxxxx
None
Vertical Horizon
All
17
Operation mode limit status
MV AC_Mode_Limit_xx_xxxxxx
No Limit Cool Only Heat Only
18
Remote controller limit status
MV AC_Remocon_Limit_xx_
xxxxxx
Enable RC Disable
RC
Conditional
RC
19
Integrated error code of both
indoor unit and outdoor unit
AI AC_Error_Code_xx_xxxxxx
Refer to list of error code
* 20 SPI setting
BV AC_SPI_xx_xxxxxx
False
True
* 21 HumanSensor setting
BV AC_MDS_xx_xxxxxx
False
True
22
AC Indoor Notify
NC AC_Notify_xx_xxxxxx
When the error occurred, send event to list of
destination in the recipient_list. (Max : 8)
Temperature setting range can be different depending on the model and the common
range is as follows:
Auto: 18˚C~30˚C
Cool: 18˚C~30˚C
Heat: 16˚C~30˚C
Fan: Temperature cannot be adjusted
Dry: 18˚C~30˚C
BACnet Point List
(*) Mark is optionally supported.