E-
63
BACnet Point List
Single AHU unit has following point list.
Instance
Number
Object
Object
Type
Object Name
Unit
Status value
Inactive Active
Text-1 Text-2 Text-3 Text-4 Text-5
1
Indoor Temperature
AI
AHU_RoomTemp_xx_xxxxxx
°C
2
Set temperature
AV AHU_Temp_Set_xx_xxxxxx
°C
3
Setting lower temperature
limit
AV AHU_Cool_LimitTemp_xx_
xxxxxx
°C
4
Setting upper temperature
limit
AV AHU_Heat_LimitTemp_xx_
xxxxxx
°C
5
The power value of an indoor
unit after the basic date
AI
AHU_Baseline_kWh_xx_
xxxxxx
kWh
6
The number of hours usage of
an indoor unit after the basic
date
AI
AHU_Baseline_Minute_xx_
xxxxxx
Minute
7
Power value within period
AI
AHU_Period_kWh_xx_
xxxxxx
kWh
8
The number of hours usage of
an indoor unit within period
AI
AHU_Period_Minute_xx_
xxxxxx
Minute
9
Power On/Off
BV AHU_Power_xx_xxxxxx
Off
On
10
Applying lower temperature
limit setting
BV AHU_Cool_Limit_set_xx_
xxxxxx
False
True
11
Applying upper temperature
limit setting
BV AHU_Heat_Limit_set_xx_
xxxxxx
False
True
12
Filter sign status
BI
AHU_FilterSign_xx_xxxxxx
False
True
13
Filter sign reset
BO AHU_FilterSign_Reset_xx_
xxxxxx
False
True
14
Operation mode status
MV AHU_Operation_Mode_xx_
xxxxxx
Auto
Cool
Heat
Fan
Dry
15
Operation mode limit status
MV AHU_Mode_Limit_xx_
xxxxxx
No
Limit
Cool
Only
Heat
Only
16
Remote controller limit status MV AHU_Remocon_Limit_xx_
xxxxxx
Enable
RC
Disable
RC
Conditional
RC
17
Integrated error code of both
indoor unit and outdoor unit
AI
AHU_Error_Code_xx_xxxxxx
Refer to list of error code
* 18
Discharge cooling set
temperature
AV AHU_DisCoolSetTemp_xx_
xxxxxx
°C
* 19
Discharge heating set
temperature
AV AHU_DisHeatSetTemp_xx_
xxxxxx
°C
* 20
Discharge current
temperature
AI
AHU_Dis_CurrentTemp_xx_
xxxxxx
°C
* 21
Humidification setting
BV AHU_Humidification_xx_
xxxxxx
Off
On
* 22
Outdoor air intake setting
BV AHU_OAIntake_xx_xxxxxx
Off
On
* 23
Outdoor cooling setting
BV AHU_OutdoorCool_xx_
xxxxxx
Off
On
* 24
Fan speed status
MV AHU_FanSpeed_xx_xxxxxx
Low
Mid
High
* 25
Set humidity status
MV AHU_SetHumidity_xx_
xxxxxx
Low
Mid
High
* 26
Current humidity status
MI AHU_CurrentHumidity_xx_
xxxxxx
Low
Mid
High
27
AHU Notify
NC AHU_Notify_xx_xxxxxx
When the error occurred, send event to list
of destination in the recipient_list. (Max : 8)
AHU Kit
(*) Mark is optionally supported.
NASAS_MIM-B17N_BACnet Gateway_IM_EN_03719A(1).indd 63