IRC Cable Specifications
At minimum, CRS recommends Shielded Category 5e STP, 4-wire twisted pair cable, for use as
communication wiring for SPS-300 series IRC systems.
NOTE:
Higher rated cables, such as Cat 6 are also acceptable
.
CAT 5e STP (Shielded Twisted Pair) cable is a high quality general purpose data
communications cable that supports standard transmission protocols such as 232, 422, 485, and
10/100 Base-T Ethernet communications. CAT 5e STP cable consists of 4 pairs of stranded,
twisted pair wire, with an overall shield foil.
Note: CRS supplies different modular connectors for use with stranded or solid cable. Use
P/N 202896 with stranded cable; use P/N 202994 with solid cable.
Do not use unshielded CAT 5e, unless run alone inside conduit.
Communication Conduit Size
Table 1-3 is a guide to the conduit size needed to fit certain numbers of communication cables:
Table 1-3: Cable/Conduit Size
Number of
Category 5 Cables
Conduit Size
(Inside Diameter)
1
0.5”
2
0.75”
4
1.0”
6
1.25”
12
1.5”
Shielded CAT5e Cable