Manual PCD7.D23x│Document 26/795; Edition E7│15.04.2005
Communication
3
3-2
Serial mode
3.1.2 Special modes (available with D23x, FW 25)
RS 232/RS 422 with XON/XOFF (R) reduced
Baudrate
Type Handshake
Control
Graphic support (HMI)
4800 bps
MC2
with
XON/XOFF (R)
Yes
RS 422 with Free Terminal Protocol (Multi-Drop)
Baudrate
Type Handshake
Control
Graphic support (HMI)
4800/9600 bps
MC0
without
-
No
* The reduced XON/XOFF mode is a save, non locking, XON/XOFF mode with the
PCD7.D23x always responding. If using XON/XOFF, it is recommended to use this re-
duced mode, especially if you notice that after some time of use you have to switch the
power off and on again to get the PCD7.D23x responding again. In this mode, the traffic
from the PCD to the PCD7.D23x is supervised by flow control, in the other direction, from
the PCD7.D23x to the PCD, there is no flow control
PCD.....
PCD7.D23x
flow control
no flow control