Change during operation: N = impossible,
Y* = possible (enabled by using ), Y= possible (enabled by using
)
-39-
FUNC
DATA
Operation method
The following four values can be selected:
0
Keypad operation [
RUN STOP
key
]
The motor runs when the
RUN
key is pressed and decelerates-to-stop when the
STOP
key is
pressed. The rotation direction depends on the FWD and REV terminals as follows:
FWD - CM short-circuited: Forward
REV - CM short-circuited: Reverse
Operation is impossible when both the FWD and REV terminals or none of them are short-circuited
with the CM terminal.
1 External signal (Digital input) (FWD, REV)
Forward operation with FWD-CM short-circuited and deceleration to stop with them open
Reverse operation with REV-CM short-circuited and deceleration to stop with them open
No operation with both FWD-CM and REV - CM short-circuited
STOP
key active (See following page chart for detail)
2
External signal (Digital input) (FWD, REV)
Forward operation with FWD-CM short-circuited and deceleration to stop with them open
Reverse operation with REV-CM short-circuited and deceleration to stop with them open
No operation with both FWD-CM and REV - CM short-circuited
STOP
key inactive (See following page chart for detail)
3
External signal (Digital input) (FWD, REV)
Forward operation with FWD-CM short-circuited and deceleration to stop with them open
Reverse operation with REV-CM short-circuited and deceleration to stop with them open
No operation with both FWD-CM and REV - CM short-circuited
STOP
key active with
special
start software (See following page chart for detail)
4
External signal (Digital input) (FWD, REV)
Forward operation with FWD-CM short-circuited and deceleration to stop with them open
Reverse operation with REV-CM short-circuited and deceleration to stop with them open
No operation with both FWD-CM and REV - CM short-circuited
STOP key inactive with
special
start software (See following page chart for detail)
Note:
This function can be changed only while the FWD and REV terminals are open.
F02
Factory
setting
Change during
operation
0
N