-15-
2 Installation and Connection
2-1 Operating Environment
Install this product at a place satisfying the conditions listed in Table 2-1-1.
Table 2-1-1 Operating environment
Item
Specifications
Place
Indoor
Ambient temperature -10 to +50 C (+14 to +122°F)
Relative humidity
5 to 95% RH (no condensation allowed)
Atmosphere
The drive must not be exposed to dust, direct sunlight, corrosive
gas, inflammable gas, oil mist, vapor, or water drops.
There must be no salt in the atmosphere.
There must be no water condensation due to sudden changes in
temperature.
Altitude
3300 feet (1000m) or less (air pressure: 86 kPa to 106 kPa)
Vibration
3 mm
2 to less than 9 Hz
9.8 m/s
2
9 to less than 20 Hz
2 m/s
2
20 to less than 55 Hz
1 m/s
2
55 to less than 200 Hz
2-2 Installation Method
¬
Tightly fasten the drive in the upright position on a strong
structure using four bolts (M4) with the product logo facing the
front. Do not install the drive upside down, or horizontally.
-
Heat is generated while the drive is operating, so the open-
ings shown in Figure 2-2-1 are necessary for the passage of
cooling air. The generated heat is convected upward by the
built-in cooling fan, so do not install the drive below any other
device that is sensitive to heat.
®
The temperature of the heat sink increases to about 90 C
while the drive is operating. Therefore, the surface behind
where the product is located must be able to withstand this
temperature increase.
!
WARNING
Install the drive on a nonflammable material such as metal,
otherwise fire could occur.
¯
When installing this drive in a control panel, carefully consider the ventilation to pre-
vent the ambient temperature of the drive from exceeding the specified value. Never
install the drive in a closed box from which heat is not radiated fully.
4"
(10 cm)
4"
(10 cm)
0.4"
(1 cm)
0.4"
(1 cm)
VM10
Drive
Figure 2-2-1
Installation Clearance