Change during operation: N = impossible,
Y* = possible (enabled by using ), Y= possible (enabled by using
)
-56-
FUNC
DATA
Data initialization
This function initializes data items set with all functions to values set in the factory.
0
Manually set value
1
Initialized (factory set value )
The display is changed from
0
to
1
when the
STOP
and
keys are pressed simultane-
ously.
When the
FUNC
DATA
key is pressed under this condition, initial data is written and a frequency set by the
built-in POT (VR) is displayed automatically.
Auto Reset
This function selects a retry operation if the drive is tripped.
0
:
Inactive
to
1
:
The auto reset count is fixed to 5 and auto reset starts when 0.5s elapses after tripping .
Auto reset is attempted only for an overcurrent/overvoltage trip that occurs during operation.
Fan stop operation
0 :
ON-OFF No control (always on)
1
:
ON-OFF Control
(The fan is turned off when the drive temperature becomes low after operation is
stopped.)
PID control (Mode select)
0
:
Inactive
1
:
Active (Normal)
2
:
Active (Inverse)
The feedback signal value (%) is displayed by assuming the full scale to be 100% when a PID control
operation is selected.
Factory
setting
Change during
operation
0
N
H20
Factory
setting
Change during
operation
0
N
H03
Factory
setting
Change during
operation
0
Y*
H04
H06
Factory
setting
Change during
operation
0
Y*
Select a PID control operation.