Change during operation: N = impossible,
Y* = possible (enabled by using ), Y= possible (enabled by using
)
-36-
FUNC
DATA
Func-
tion
code
No.
Name
Setting range
Unit
Min.
unit
Factory
setting
Change
during
operation
User
setting
P00
Motor characteristics
0 to 10
-
-
2
Y
Func-
tion
code
No.
Name
Setting range
Unit
Min.
unit
Factory
setting
Change
during
operation
User
setting
H01
Operation time
Operation time accumulation
100Hr
1
0
-
H02
Trip history
The contents of the last four alarms are
displayed sequentially.
-
-
---
-
H03
Data initialization
1: Initialized
(return to factory setting value)
-
-
0
N
H04
Auto-reset
0: Inactive
1: Active (5 times fixed)
-
-
0
Y*
H06
Fan Stop Operation
0: Inactive
1: Active
-
-
0
Y*
H20
PID control
(
Mode select)
0: Inactive
1: Active (Normal operation)
2: Active (Inverse operation)
-
-
0
N
H21
(Feedback signal)
0:
Terminal
[12]
(0 to +10Vdc)
Input
1:
Terminal
[C1]
(4 to 20mAdc)
Input
2:
Terminal [
12]
(+1 to +5Vdc)
Input
-
-
1
N
H22
(
P-gain
)
0.01 to 10.0 times (1to1000%)
-
0.01
0.01
Y
H23
(
I-gain)
0.0s :
Inactive
0.1 to 999s
s
0.1
0.0
Y
H24
(D-gain)
0.00s :
Inactive
0.01 to 10.0s
s
0.01
0.00
Y
H25
(
Feedback filter)
0.0 to 60.0s
s
0.1
0.5
Y
H: High Performance Functions
P: Motor Parameters