Specification of SN200G high-performance vector convertor
Parameter description
- 95 -
FM terminal is a programmable multiplexing terminal can be used as high-speed pulse output terminal (FMP), the
switch can also be used as open collector output terminal (FMR).
As the pulse output FMP, the maximum output pulse frequency is 100kHz, FMP-related functions can be found P5-06
instructions.
P5-01
FMRI function selection (open collector output terminal)
Factory default
0
P5-02
Relay output function selection (T / A-T / B-T / C)
Factory default
2
P5-03
Expansion card relay output function selection (P / A-P / B-P / C)
Factory default
0
P5-04
DO1 output function selection (open collector output terminal)
Factory default
1
P5-05
Expansion card DO2 output function selection
Factory default
4
The five function code is used to select the five digital outputs function, where T / A-T / B-T / C and P / A-P / B-P / C,
respectively on control board and expansion card relay.
Multi-function output terminal functions are as follows:
Set point
Function
Explanation
0
No output
Output terminal has no function
1
Inverter running
Indicates the drive is in running state, the output frequency (can be zero),
ON signal is output.
2
Fault output (downtime)
When the drive fails and downtime, it outputs ON signal.
3
Frequency level detection
output FDT1
Please refer to the function code P8-19, P8-20 description.
4
Frequency arrival
Please refer to the function code P8-21 description.
5
Zero speed operation (no output
shutdown)
Inverter running and the output frequency is 0, output ON signal. When
the drive is shut down, the signal is OFF.
6
Motor overload pre-alarm
Before the motor overload protection, according to the overload pre-
alarm threshold value judgment over pre-alarm threshold value output
ON signal. Motor overload parameter settings see Function Code P9-00
~ P9-02.
7
Inverter overload pre-alarm
Before the inverter overload occurs 10s, output ON signal.
8
Set counting value arrival
When the count value reaches the value of PB-08 set, output ON signal.
9
Designated counting value
arrival
When the count value reaches the value of PB-09 group,
output ON signal. PB reference counting function group
Function
10
Length arrival
When detecting the actual length exceeds PB-05 set length, output ON
signal.
11
PLC Complete cycle
After simple PLC completes one cycle, the output of a pulse width of
250ms.
12
Total running time arrival
When the accumulated running time exceeds the time set by P8-17, output
ON signal.
13
Frequency is defined in
When the set frequency exceeds the upper limit frequency or lower
frequency, and output frequency has reached the upper limit frequency
or lower frequency, the output ON signal.
14
Torque limiting
Drive under the speed control mode, when the output torque reaches
the torque limit, the inverter is in the stall protection status, and ON
signal is output.
15
Ready to run
When the inverter main circuit and control circuit power supply has
stabilized, and the drive does not detect any fault information, the drive
is in an operational state, output ON signal.