Specification of SN200G high-performance vector convertor
Parameter description
- 77 -
P1 group: Parameters of 1
st
motor
P1-00
Type selection of motor
Factory default
0
Setting
range
0
Common asynchronous motor
1
Variable frequency asynchronous motor
P1-01
Rated power
Factory default
Depend on machine type
Setting range
0.1kW
~
1000.0kW
P1-02
Rated voltage
Factory default
Depend on machine type
Setting range
1V
~
400V
P1-03
Rated current
Factory default
Depend on machine type
Setting range
0.01A
~
655.35A (convertor power <=55kW)
0.1A
~
6553.5A (convertor power >55kW)
P1-04
Rated frequency
Factory default
Depend on machine type
Setting range
0.01Hz
~
max. frequency
P1-05
Rated speed
Factory default
Depend on machine type
Setting range
1rpm
~
65535rpm
The code for the motor nameplate parameters, both by VF control and vector control, are needed
to accurately set the relevant parameters according to the motor nameplate.
In order to obtain better VF or vector control performance, the need for parameter tuning, and
the accuracy of adjustment results, and properly set motor nameplate parameters closely.
P1-
06
Stator resistance of asynchronous motor
Factory default
Depend on machine type
Setting range
0.001Ω
~
30.000Ω
P1-
07
Rotor resistance of asynchronous motor
Factory default
Depend on machine type
Setting range
0.001Ω
~
65.535Ω (convertor power <=55kW)
0.0001Ω
~
6.5535Ω (convertor power >55kW)
P1-
08
Leakage inductive reactance of
asynchronous motor
Factory default
Depend on machine type
Setting range
0.01mH
~
655.35mH (convertor power <=55kW)
0.001mH
~
65.535mH (convertor power >55kW)
P1-
09
Mutual inductive reactance of
asynchronous motor
Factory default
Depend on machine type
Setting range
0.1mH
~
6553.5mH (convertor power <=55kW)
0.01mH
~
655.35mH (convertor power >55kW)
)
P1-
10
No-load current of asynchronous motor
Factory default
Depend on machine type
Setting range
0.01A
~
P1-03 (convertor power <=55kW)
0.1A
~
P1-03 (convertor power >55kW)
P1-06 ~ P1-10 is asynchronous motor parameters, these parameters generally do not have the motor
nameplate, auto-tuning to get through the drive. Among them, “Induction Motor static tuning” can only
get three parameters P1-06 ~ P1-08. But the “asynchronous motors complete tuning” can be obtained here
except all five parameters, you can also get the encoder phase sequence, current loop PI parameters and
others.