Specification of SN200G high-performance vector convertor
Parameter description
- 113 -
P8-31
Any reached frequency detection range 1
Factory default
0.0%
Setting range
0.0% to 100.0% (maximum frequency)
P8-30
Any reached frequency detection value 2
Factory default
50.00Hz
Setting range
0.00Hz ~ maximum frequency
P8-31
Any reached frequency detection range 2
Factory default
0.0%
Setting range
0.0% to 100.0% (maximum frequency)
When the output frequency of the inverter, when arriving at any frequency detection value detected positive and negative
amplitude range, multi-DO output ON signal.
SN200G arrival frequency detection provides two sets of arbitrary parameters were set frequency value and frequency
detection range. 6-20 schematic diagram for the function.
Operating frequency
Any arrival frequency
time
Any arrival frequency
detection signal DO or relay
OFF
ON
ON
OFF
OFF
Figure 6-20 arbitrary frequency detection arrival schematic
P8-34
Zero-current detection level
Factory default
5.0%
Setting range
0.0%
~
300.0% (motor rated current)
P8-35
Zero-current detection delay time
Factory default
0.10s
Setting range
0.00s
~
600.00s
When the inverter output current is less than or equal to zero current detection level and lasts longer than the zero current
detection delay time, the inverter output multifunction DO ON signal. Figure 6-21 zero current detection Fig.
Frequency detection width
Frequency detection width