Specification of SN200G high-performance vector convertor
Parameter description
- 130 -
PB-04 Triangular wave rise time coefficient
Factory default
50.0%
Setting range
0.0%
~
100.0%
Swing frequency cycle: a complete wobble cycle time value.
Triangular wave rise time coefficient PB-04, a triangular wave rising relatively wobble cycle PB-03 percentage of the time.
Triangular wave rise time = Swing frequency cycle PB-03 × triangular wave rising time coefficient PB-04, in seconds.
Triangular wave falling time = Swing frequency cycle PB-03 × (1- triangle wave rise time coefficient PB-04), in seconds.
PB-05
Set length
Factory default
1000m
Setting range
0m
~
65535m
PB-06
Actual length
Factory default
0m
Setting range
0m
~
65535m
PB-07
Number of pulses per meter
Factory default
100.0
Setting range
0.1
~
6553.5
The above function codes for fixed-length control.
Length information you need to enter through the multifunction digital terminal acquisition, the number of sampling pulses
terminals and the number of pulses per meter PB-07 phase in addition calculated to give actual length PB-06. When the
actual length is greater than the set length PB-05, multi-function digital output DO “Length arrival” ON signal.
Fixed length control process, by multi-function terminal DI carried out the length of the reset operation (DI function
selection 28). Please refer to P4-00 ~ P4-09.
Applications need to set the corresponding input terminal function set to “length count input” (function 27), at higher pulse
frequency must be used DI5 port.
PB-08
Set count value
Factory default
1000
Setting range
1
~
65535
PB-09
Designated counting value
Factory default
1000
Setting range
1
~
65535
The count value required by multifunction digital input terminal acquisition. Applications need to set the corresponding input
terminal function set to “counter input” (function 25), at higher pulse frequency must be used DI5 port.
When the count value reaches the set count value PB-08, multi-function digital output DO “reaching the set count” ON
signal, then stop counting.
When the count reaches the designated counting value PB-09, the multi-function digital output DO “reaching the set count”
ON signal, when the counting continues until “set count value” counter stopped.
Specified count number PB-09 should not be greater than the set counter value PB-08. Figure 6-29 is reaching the set count
and the count value of the specified schematic reach capabilities.