Specification of SN200G high-performance vector convertor
Functional parameter table
- 47 -
Code
Name
Setting range
Default Change
P5-06
FMP output function selection
0: Operation frequency
1: Setting frequency
2: Output current
3: Output torque
4: Output power
5: Output voltage
6: PULSE input
(100.% corresponds to 100.0kHz)
7: AI1
8: AI2
9: AI3 (expansion card)
10: Length
11: Value
12: Communication setting
13: Motor speed
14: Output current (100.0% is 1000.0A)
15: Output voltage (100.0% is 1000.0V)
16: Reserve
0
☆
P5-07
AO1 output function selection
0
☆
P5-08
Output function selection of
expansion card AO2
1
☆
P5-09
FMP maximum output frequency 0.01kHz
~
100.00kHz
50.00kHz
☆
P5-10
AO1 zero offset coefficient
-100.0%
~
+100.0%
0.0%
☆
P5-11
AO1 gain
-10.00
~
+10.00
1.00
☆
P5-12
Zero offset coefficient of
expansion card AO2
-100.0%
~
+100.0%
0.0%
☆
P5-13
AO2 gain of expansion card AO2 -10.00
~
+10.00
1.00
☆
P5-17
FMR output delay time
0.0s
~
3600.0s
0.0s
☆
P5-18
RELAY1 output delay time
0.0s
~
3600.0s
0.0s
☆
P5-19
RELAY2 output delay time
0.0s
~
3600.0s
0.0s
☆
P5-20
DO1 output delay time
0.0s
~
3600.0s
0.0s
☆
P5-21
DO2 output delay time
0.0s
~
3600.0s
0.0s
☆
P5-22
Valid state selection of DO
output terminal
0: positive logic
1: negative logic
Bit: FMR
Ten bit: RELAY1
Hundred bit: RELAY2 Thousand bit: DO1
Ten Thousand bit: DO2
00000
☆
Start/Halt control of P6 group
P6-00
Start mode
0: Direct start
1: Speed tracking restart
2: Start pre-excitation (AC asynchronous
motor)
0
☆
P6-01
Speed tracking mode
0: Start from stop frequency
1: Start from zero speed
2: Start from maximum frequency
0
★
P6-02
Speed tracking speed
1
~
100
20
☆
P6-03
Start frequency
0.00Hz
~
10.00Hz
0.00Hz
☆