Specification of SN200G high-performance vector convertor
Functional parameter table
- 40 -
P0-07
Frequency source superimposed
selection
Bits: Frequency source selection
0: Main frequency source X
1: Main and auxiliary operation result
(Operation relation depends on decimal)
2: Switch of main frequency source X and
auxiliary frequency source Y
3: Main frequency source X, main and
auxiliary operation result switch
4: Auxiliary frequency source Y, main and
auxiliary operation result switch
Decimal: operation relation of main and
auxiliary frequency source
0: Main + auxiliary
1: Main-auxiliary
2: Max. of the two
3: Min. of the two
00
☆
P0-08
Preset frequency
0.00Hz
~
maximum frequency (P0-10)
50.00Hz
☆
P0-09
Running direction
0 : Same direction
1 : Opposite direction
0
☆
P0-10
Maximum frequency
50.00Hz
~
600.00Hz
50.00Hz
★
P0-11
Upper frequency source
0: P0-12 setting
1: AI1; 2: AI2; 3: AI3; 4: PULSE setting
5: Communication given
0
★
P0-12
Upper frequency
Upper frequency P0-14
~
maximum
frequency P0-10
50.00Hz
☆
P0-13
Upper frequency offset
0.00Hz
~
maximum frequency P0-10
0.00Hz
☆
P0-14
Lower frequency
0.00Hz
~
upper frequency P0-12
0.00Hz
☆
P0-15
Carrier frequency
0.5kHz
~
16.0kHz
machine type
☆
P0-16
carrier frequency adjusts with
temperature
0: no
1: yes
1
☆
P0-17
Acceleration time 1
0.00s
~
65000s
machine type
☆
P0-18
Deceleration time 1
0.00s
~
65000s
machine type
☆
P0-19
Acceleration/Deceleration time
unit
0: 1s
1: 0.1s
2: 0.01s
1
★
P0-21
Auxiliary superimposed
frequency source bias frequency
0.00Hz
~
maximum frequency P0-10
0.00Hz
☆
P0-22
Resolution frequency command 1: 0.1Hz
2: 0.01Hz
2
★
P0-23
Digital setting frequency stop
memory selection
0: no memory 1: memory
0
☆
P0-24
Motor selection
0: Motor 1, 1: Motor 2
0
★
P0-25
Acceleration/Deceleration time
reference frequencies
0: maximum frequency (P0-10)
1: Set frequency
2: 100Hz
0
★
P0-26
Frequency command in operation
UP/DOWN standard
0: Operating frequency, 1: Set frequency
0
★
Code
Name
Setting range
Default Change