Specification of SN200G high-performance vector convertor
Product information
- 11 -
2.4 Technical specifications
Figure 2-2 Technical specifications of frequency convertor
Items
Specifications
Basic
functions
Highest frequency
Vector control: 0
~
300Hz
V/F control: 0
~
3200Hz
Carrier frequency
0.5kHz
~
16kHz
Adjust carrier frequency automatically based on load characteristic
Input frequency resolution
Number setting: 0.01Hz
Simulation setting: highest frequency ×0.025%
Control mode
SVC
FVC
V/F control
Starting torque
G-style machine: 0.5Hz/150% (SVC); 0Hz/180% (FVC)
P-style machine: 0.5Hz/100%
Speed regulation range
1: 100 (SVC)
1: 1000 (FVC)
Speed stabilizing precision
±0.5% (SVC)
±0.02% (FVC)
Torque control precision
±5% (FVC)
Overload capacity
G-style machine: 150% rated current at 60s; 180% rated current at 3s
P-style machine: 120% rated current at 60s; 150% rated current at 3s
Torque promotion
Automatic torque promotion; manual torque promotes by 0.1%~30.0%
V/F curve
Three ways: linear type; multipoint type; N
th
power type V/F curve
(1.2 power, 1.4 power, 1.6 power, 1.8 power, 2 power)
V/F separation
2 ways: full separation, semi-separation
Acceleration/deceleration
curves
Linear or S-curve acceleration/deceleration way.
Four kinds of acceleration/deceleration time
Acceleration/deceleration time range: 0.0~6500.0s
DC braking
DC braking frequency: 0.00Hz~maximum frequency; Braking time:
0.0s~36.0s braking action; Current value: 0.0%~100.0%
Inching control
Inching frequency range: 0.00Hz~50.00Hz;
Inching acceleration/deceleration time 0.0s~6500.0s
Simple PLC, multi-stage
velocity operation
Realize 16-stage velocity operation at most through built-in PLC or
control terminal
Built-in PID
Easy to realize process control, closed-loop control system
Automatic voltage regulation Keep constant output voltage automatically if any change of network
voltage
Overvoltage, overcurrent,
stalling control
Limit current/voltage automatically during operation, prevent frequent
tripping caused by over-current and over-voltage
Fast current-limiting function Reduce over-current fault, protect normal operation of convertor
Torque limit and control
“Nawy” character limit torque during operation,
prevent frequent overcurrent tripping, closed-loop
vector mode can realize torque control