HOW TO DETERMINE THE POWER SUPPLY CABLE

To determine the size of the  power cable for the submersible motor, the
following information is required:
- V: Rated value of input voltage (V)
- I: Current consumption of motor, indicated on the motor rating plate (A)
- L: Length of line
- Cosf: Motor power factor (indicated on the rating plate)
- Room temperature (

°

C)

- Current carrying capacity of cable

Choose the minimum cross-section from the value I of the rated current of
the motor, according to the maximum current carrying capacities of cables
indicated in Table 4. Quadripolar cables are used for cables up to a cross-
section of  35 mm˝, while unipolar cables are recommended for larger cross-
sections.
Table 4 indicates maximum current carrying capacities of cables according
to the number of lines that are connected in parallel:

just one line

direct motor starting
stator motor starting

two lines

star/delta starting
two lines in parallel in order to use lighter cables

four lines

star/delta starting with double lines.

For star/delta starting, the current in the cables is equal to the rated current
divided by 1,73.
The maximum current carrying capacities of the cables shown in Table 4
apply for room temperatures of 30

°

 C. If the room temperature is different

apply the correction factor.
The final choice of the cross-section of the cable is carried out by verifying
the voltage drop along the power line, by applying the following relation:

V% = 173 x I x L x (R x cos

 

+ X x sen

) / V

V% voltage drop in percent (must not exceed is 5%)

I = rated current in Amperes (for star/delta starting the value is 58%)

L = lenght of line in meters (for star/delta starting the lenght is double)

cos

 = power factor (indicated on the motor rating plate)

sen

 = (   1-cos2

)

R,X = resistance and reactance of cable in ohm/metre (indicated in tab.4)

V = input voltage.

The following tables define the maximum lenght of the cables depending
on  the  power  of  the  motor,  input  voltage,  the  size  of  the  cables,  all  at  a
room temperature of 30

°

 C.

TAB. 4

Electrical cables - Direct starting - 3 phase motor

1,5

2,5

4

6

10

16

25

35

60

70

95

120

150

185

240

18

24

32

41

57

76

102

126

168

213

258

300

350

392

461

16

21

28

36

50

68

89

110

146

185

224

261

305

341

401

14

19

26

33

46

61

82

101

134

170

206

240

280

314

369

15,1

9,08

5,63

3,73

2,27

1,43

0,907

0,654

0,473

0,326

0,236

0,188

0,153

0,123

0,0943

0,118

0,109

0,101

0,0955

0,0861

0,0817

0,0813

0,0753

0,101

0,0955

0,0955

0,0939

0,0928

0,0908

0,0902

Type of cable

Rated

cross-section

mm

2

Max. cable capacity

1 lines

2 lines     4 lines

A

A

A

/Km

/Km

Resistance

Reatance

R

X

178

265

439

706

1060

231

344

570

915

531

791

611

908

691

1028

127

189

313

503

755

167

248

412

660

990

378

563

834

435

847

1073

500

743

95

142

235

377

566

822

131

194

321

515

772

284

422

700

335

498

825

390

580

961

63

94

156

251

377

615

963

87

129

241

344

515

636

189

282

467

750

223

332

550

883

260

387

641

1027

51

76

127

203

305

497

780

67

99

164

263

395

642

1003

153

228

377

606

911

176

261

433

698

1045

199

296

491

787

39

59

97

156

234

382

599

926

52

77

127

204

307

499

779

117

175

290

465

899

135

201

333

534

802

155

230

381

611

917

220

240

380

400

415

220

240

380

400

415

220

240

380

400

415

220

240

380

400

415

220

240

380

400

415

220

240

380

400

415

1,9

1,7

1,1

1,0

1,0

2,7

2,5

1,6

1,5

1,4

3,6

3,3

2,1

2,0

1,9

5,4

5,0

3,1

3,0

2,9

6,6

6,1

3,8

3,6

3,5

8,5

7,8

4,9

4,7

4,5

0,5

0,75

1

1,5

2

3

0,37

0,55

0,75

1,1

1,5

2,2

HP

kW

V

A

1

1,5

2,5

4

6

10

16

25

Rated poxer

of motor

Rated

voltage

Rated

current

Cable section (mm

2

) - Quadripolar cables

Max. cable lenght with 5% voltage drop

Quadripole

Quadripole

Quadripole

Quadripole

Quadripole

Quadripole

Quadripole

Quadripole

Unipolar

Unipolar

Unipolar

Unipolar

Unipolar

Unipolar

Unipolar

Summary of Contents for MS-152

Page 1: ...I N CE DE CONFORMIDAD Contient DECLARATION DE CONFORMITE LIBRETTOISTRUZIONI MOTORISOMMERSI 6 8 10 12 INSTRUCTIONMANUALFOR SUBMERSIBLEMOTORS 6 8 10 12 BEDIENUNGSHANDBUCH TAUCHMOTOREN 6 8 10 12 NOTICEDE...

Page 2: ...n No toque el motor cuando est funcionando Avant d effectuer n importe quelle op ration d brancher les c bles lectriques d alimentation Ne pas toucher le moteur durant son fonctionnement Non utilizza...

Page 3: ...person and or property if instructions are not followed GEFAHR Das Nichtbeachten der Vorschriften kann zu Personen und oder Sachsch den f hren PELIGRO El no respetar la prescripci n comporta un riesg...

Page 4: ...sorgf ltig zu lesen und die Anweisungen genau einzuhalten F r Personen und oder Sachsch den die auf die Nichtbeachtung dieser Anweisungen zur ckzuf hren sind lehnen wir jegliche Haftung ab Die Anweisu...

Page 5: ...filo protetto contro gli effetti della sommersione Tutti i motori possono essere indifferentemente impiegati in entrambi i sensi di marcia destroso o sinistroso SAER submersible motors are asynchronou...

Page 6: ...cient must also be applied to these motors if this threshold is to be exceeded please refer to table 2 Die Tauchmotoren k nnen gem NEMA Norm im Dauerbetrieb mit der Nennleistung betrieben werden sowei...

Page 7: ...nale viene precisato il materiale isolante dei fili di avvolgimento PVC oppure PE2 Il filo di avvolgimento in rame isolato con particolari resine termoplastiche quello normalmente utilizzato in PVC cl...

Page 8: ...quanto il naturale flusso di acqua provocato dal risucchio della pompa ed in parte dai movimenti convettivi dovuti al riscaldamento del fluido all esterno del motore ne garantiscono il raffreddamento...

Page 9: ...he motor is filled with liquid coolant WARNUNG Sicherstellen dass der Motor mit K hlfl ssigkeit ADVERTENCIA Verificar que el motor est lleno de l quido refrigerante MISE EN GARDE S assurer que le mote...

Page 10: ...la pueden instalarse tambi n en horizontal dicha aplicaci n suele emplearse en dep sitos o cubas Es fundamental garantizar al motor un buen enfriamiento ver apartado anterior para ello el motor deber...

Page 11: ...opriate lifting equipment Any knock or impact can damage it even if there is no sign of external damage GEFAHR Die Pumpe ist mit geeigneten Hubmitteln zu tr sportieren ein Absturz der Elektopumpe sowi...

Page 12: ...oni Nel caso dell allacciamento dei motori sommersi la posa pu considerarsi in cunicolo per il tratto di salita lungo il pozzo e a parete o area per il tratto esterno in entrambi i casi l ambiente dev...

Page 13: ...oit tre humide mouill raison pour laquelle la norme exige des c bles gain s 5 1 SCELTA DEL CAVO ELETTRICO CHOOSING ELECTRICAL CABLES KABELAUSWAHL ELECCI N DEL CABLE EL CTRICO CHOIX DU CABLE ELECTRIQUE...

Page 14: ...de los cables son definidas por las Normativas CEI UNEL y los datos relativos son proporcionados en funci n de temperaturas ambiente del 30 C En aquellas aplicaciones en las que las temperaturas ambi...

Page 15: ...esistenza e reattanza del cavo in ohm metro indicati in tab 4 V tensione di alimentazione in Volt Nella tabella qui a fianco sono definite le lunghezze massime dei cavi in funzione della potenza dei m...

Page 16: ...tance of cable in ohm metre indicated in tab 4 V input voltage The following tables define the maximum lenght of the cables depending on the power of the motor input voltage the size of the cables all...

Page 17: ...len finden Sie die maximalen L ngen der Kabel in Abh ngigkeit von der Leistung des Motors der Anschlu spannung des Kabelschnittes mit Umgebungstemperatur von 30 C TAB 4 Tabelle Kabell nge Direktanlauf...

Page 18: ...lo la longitude es doble cos factor de potencia indicado en la placa de caracter sticas del motor sen 1 cos2 R X resistencia y reactancia del cable en ohm metro indicadas en la Tabla n 4 V tensi n de...

Page 19: ...la plaquette du moteur sen 1 cos2 R X r sistance et r actance du c ble en ohms m tres indiqu es sur le Tableau Nr 4 V Tension d alimentation en Volt Les tableaux suivants indiquet les longueurs maxim...

Page 20: ...66 108 169 261 356 466 642 842 1008 69 110 166 270 424 655 892 76 122 184 299 470 726 989 82 132 198 322 506 781 1064 77 121 186 254 332 458 601 719 840 985 56 92 144 222 302 395 545 715 856 1000 94 1...

Page 21: ...353 423 495 581 694 389 537 708 845 990 164 216 296 391 469 548 644 769 431 595 762 938 1097 177 232 320 421 505 590 693 827 464 641 842 1010 106 127 149 175 209 117 162 213 255 298 350 418 127 152 1...

Page 22: ...78 69 108 166 226 296 408 535 641 749 878 1045 70 105 172 270 416 567 742 1024 78 117 190 299 461 628 823 84 126 205 321 497 676 886 79 122 167 219 302 397 476 556 653 779 94 146 198 260 359 472 566 6...

Page 23: ...2 146 171 200 238 135 186 244 293 342 401 477 95 129 169 234 306 367 428 502 598 339 467 613 734 857 1004 105 143 188 259 339 406 475 556 662 376 518 679 813 949 73 113 154 202 279 365 437 511 599 713...

Page 24: ...0 92 138 225 352 541 735 953 77 123 185 301 472 726 985 84 135 202 329 515 793 1077 79 131 211 316 515 805 64 100 155 210 273 374 487 580 674 785 927 78 117 191 299 461 627 814 94 141 230 360 555 755...

Page 25: ...4 829 963 175 226 310 402 478 556 645 761 453 620 805 957 191 248 339 440 523 607 705 832 495 677 879 220 298 387 529 687 817 949 774 111 129 150 177 105 144 187 222 258 299 353 157 214 278 331 385 44...

Page 26: ...49 996 36 59 95 142 232 364 562 766 48 79 127 191 311 488 754 52 86 139 209 340 533 824 81 135 217 326 531 833 27 40 65 103 159 216 283 390 512 612 715 838 50 80 120 195 306 473 645 844 40 67 107 161...

Page 27: ...5 610 719 428 586 761 904 123 190 258 335 458 594 707 821 953 669 915 62 81 96 111 130 153 91 124 161 192 223 259 305 77 105 136 185 241 286 333 386 456 271 371 482 573 665 773 911 103 140 182 249 323...

Page 28: ...lap Remove the internal sheathing of the wires for a length of 10 20 mm according to the section of the wire and then complete connections using crimp on connectors Follow the instructions provided wi...

Page 29: ...ese must be connected to the terminals for the controls If the motor is designed for dual voltage operation e g 220V 380V there are two series of three wires each in addition to the earth connection w...

Page 30: ...dare un breve impulso elettrico L elettropompa tender ad assumere un senso di rotazione opposto a quello dell albero motore per causa del contraccolpo Verificare se il senso di rotazione dell albero...

Page 31: ...ituazioni in cui si rende necessario l intervento di manutenzione Per potere individuare il problema in maniera rapida ed agire in modo corretto seguire le istruzioni della tabella al punto 8 DISFUNZI...

Page 32: ...cualquier operaci n de mantenimiento desconectar la electrobomba de la red el ctrica o del eventual generador DANGER Avant toute op ration d entretien d brancher l lectropompe de la prise de secteur...

Page 33: ...relay is not correctly calibrated Falsche Relais Eichung El rel no est bien calibrado Le relais n est pas r gl Rifare la taratura del rel Reset the calibration of the thermic relay Relais neu einstell...

Page 34: ...tor estan bloqueados La pompe ou le moteur sont bloqu s Smontare e revisionare Disassemble and overhaul it Abbauen und berholen Desmontar y revisar D montez et r visez Il collegamento del motore non c...

Page 35: ...pirante The water level is too close to the inlet Wasserstand dem Saugstutzen zu nahe Nivel de agua demasiado cerca de la boca de aspirac on Le niveau du puits est trop proche de l orifice d aspiratio...

Page 36: ...cessaire au moteur pendant la phase de d marrage Le tableau suivant conseille les dimensions des groupes lectrog nes en fonction des modalit s de d marrage de l lectropompe Motore tipo Motor type Mot...

Page 37: ...2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 1 5 2 2 3 4 5 5 7 5 9 11 13 15 18 5 22 26 30 37 13 15 18 5 22 26 30 37 45 52 55 60 67 75 83 92 110 75 92 110 132 150 170 185 150 185 220 260 300 2 3 4 5 5 7 5 10 12 5...

Page 38: ...ta assiale Max axial thrust N Peso motore Motor weight kg kW HP D mm L mm 8 8 8 8 8 8 8 8 8 8 8 8 10 10 10 10 10 12 12 12 12 12 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 5 5 7 5 11 15 18 5 22 26 30...

Page 39: ...TSERKL RUNG Die Firma SAER Elettropompe S p A mit Firmensitz in via Circonvallazione 22 42016 Guastalla RE Italien best tigt hiermit da die Tauchmotoren der Serie MS MSX MSB den folgenden Richtlinien...

Page 40: ...hne Benachrichtigung zu ndern Saer se reserva el derecho de modificar los datos indicados en este manual sin previo aviso Saer se r serve le droit de modifier sans pr avis les donn es techniques dans...

Reviews: